Wire Reference Chart; Fresh Air - Radio Thermostat CT80 Install Manual

Thermostat
Hide thumbs Also See for CT80:
Table of Contents

Advertisement

12
Humidifi er -
To use the CT80 internal humidistat to control an external
humidifi er unit, connect it as shown. Connect the H
terminal to the control leg of the humidifi er relay. This
allows H to turn the humidifi er ON and Off.
De-Humidifi er -
To use the CT80 internal humidistat to control an external
De-humidifi er unit, connect it as shown. Connect the DH
terminal to the control leg of the dehumidifi er relay. This
allows DH to turn the dehumidifi er ON and Off.

Fresh Air -

The Fresh Air feature uses the EX relay to control a baffl e
on a fresh external air source. Connect the 24VAC baffl e
to C and EX terminals.
FOR FRESH AIR BAFFLE
CT80
RH
EX
FURNACE
R
POWER
C
13

WIRE REFERENCE CHART

Your Wires
CT80 Terminal
R or V or VR
RH and RC Single power for HEAT and COOL
RH or 4
RH Power for HEAT (RH not connected to RC jumper clip removed)
RC
RC Power for COOL (RH not connected to RC jumper clip removed )
W
W Heat control
W2
W2 2nd stage HEAT or heat pump auxiliary heat
W3
W3 3rd stage HEAT or 2nd stage of 2 stage auxiliary heat
?
A 3rd wire for zoned hot water heat (see zoned systems pg14)
Y
Y COOL control or 1st stage compression for heat pump.
Y2
Y2 2nd stage COOL control or 2nd stage compression for a heat pump
G or F
G FAN control
C or X
C Common 24VAC power (to power thermostat ) NOTE: TRANE uses B for this connection
E
n/a Emergency heat (do not connect, tape off)
L
n/a System monitor (do not connect, tape off)
T
n/a Outdoor sensor (do not connect, tape off)
H
External Humidifi er
DH
External De-Humidifi er
EX
External fresh air baffl e
B or
B Heat pump changeover (cool to heat, powered in heat)
O
O Heat pump changeover (heat to cool, powered in cool)
B and O
products) DO NOT CONNECT B to B terminal, connect B to C
terminal. If not a Trane product tape off B.
Lennox Heat Pump
V or VR or R
RH Power for HEAT
M or Y
Y
Y or W or W2
W2
F or G
G
R or O
OX or X2 or C
BAFFLE
IMPORTANT: If there are both B and O wires (Trane pump
Trane Products [American Standard]
B
W or W1 or X2
C
FOR EXTERNAL HUMIDIFIER
or DEHUMIDIFIER USING
HVAC SYSTEM's 24
CT80
RH
H or DH
FURNACE
R
POWE R
C
24VAC
H or DH
RELAY
FOR EXTERNAL HUMIDIFIER
or DEHUMIDIFIER USING
USING 24VAC ADAPTER
CT80
RH
H or DH
FURNACE
R
POWER
C
AC
ADPT
H or DH
RELAY
C
W2
12
PG
VAC
To HUMIDIFIER
or
DEHUMIDIFIER
To HUMIDIFIER
or
DEHUMIDIFIER
13
PG

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents