GUIDE SPECIFICATIONS

EACH UNIT SHALL BE:

Covered by a 1-year limited parts warranty on the com-
plete unit.
In current production with published literature available
to check performance, limitations, specifications, power
requirements, dimensions, operation and appearance,
and
Equipped with a V-belt drive that:
a.
Is rated at least 25% above the required HP.
b.
Will permit the blower RPM to be adjusted to meet
the exact CFM requirement of the system.

EACH UNIT ENCLOSURE SHALL HAVE:

A steel angle frame to provide the rigid support required
for shipping, rigging and years of dependable operation.
Exterior panels of 18 gauge steel, finished with baked
enamel to provide a long lasting quality appearance
Removable panels to provide easy access to the internal
components for maintenance and service, and,
A filter rack with 1" filters.
Subject to change without notice. Printed in U.S.A.
Copyright © by Unitary Products Group 2000. All rights reserved.
Unitary
Products
Group
THE DIMENSIONS OF EACH UNIT SHALL NOT
EXCEED THOSE SPECIFIED.

THE BLOWER MOTOR SHALL:

Be mounted within the insulated cabinet to minimize the
transmission of sound to the surrounding space, and
Have a service factor of 1.15

THE EVAPORATOR COIL SHALL:

Consist of copper tubes arranged in staggered rows,
mechanically expanded into aluminum fins,
Be draw-through, and
Include factory-mounted distributors, expansion valves
and solenoid valves for both capacity reduction and
pumpdown.

THE BLOWER WHEELS SHALL

Be dynamically balanced to minimize the levels of sound
and vibration generated by the unit