Fan Motor - Airbloc ACR Instruction Manual

Acr recessed aircurtain electrically heated, ambient & lphw
Table of Contents

Advertisement

4.6
Factory Wiring - Electrically heated 6 & 9kW SINGLE PHASE ONLY
J1
Overheat
L= LEFT SIDE
R= RIGHT SIDE
T= TOP ELEMENT
M= MIDDLE ELEMENT
B= BOTTOM ELEMENT
Elements
Elements
Contractors
Terminal
The element output is connected to the right and left
side of each terminal block marked "AC1-T1", "AC2-T1",
AC1-T2", "AC2-T2", "AC1-T3" and "AC2-T3"
The fan output is connected to a 4 way connector
marked "N", "F1", "F2" and "F3".
The thermal trip is connected to a 2 way connector
marked "T1" & "T2"
S1
S2
D1
D2
B1
B2
T1
T2
R(B)
L(M)
L(B)
R(M)
L(T)
R(T)
E
N
Pcb Terminal
L1
L2
L3
L
T1
T2
N
F1
F2
F3
J1
20
GND
DATA
+12V

Fan Motor

Description
Heater Elements one third
Heater Elements one third
Heater Elements one third
Thermal Overheat trip
Thermal Overheat trip
Neutrals
Fan - low speed
Fan - medium speed
Fan - high speed
Factory BMS link

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents