The SK-5208 control panel can be programmed from either the on-board annunciator or the
SK-5235 remote annunciator. You must be in Programming Mode to program the control
panel.
4.1

Keypad Operation During Programming

This section describes the function of the buttons on the keypad while in program mode.
Operation/Button
Enter Step Programming
mode
Moving through
programming
Exit Step Programming
Down Arrow
Enter Button
Left Arrow
Right Arrow
Silence Button
Up Arrow
* Button
#
# Button
P/N 151204
2
7
Press
, followed by installer level code (the factory programmed code is
123456 or 5208). See Section 4.2.6 for user code programming information.
When you have entered programming correctly, the display will show Zone 1 Options. Press
to move to next programming option. See Table 4-4 for list of programming options
(column 1) and their menu items (column 2).
When the display shows the option you wish to program press
option.
If you receive a trouble beep and the message TRY AGAIN appears you are not
using an installer level code.
Press
. You are prompted to save programming changes. The default is No. Press the
up or down arrow to select Yes to save programming changes. Press Enter to complete the
save and return to normal operation mode.
Accepts the entered data and scrolls down to the next menu item.
Accepts the entered data and scrolls down to the next menu item.
Scrolls backwards through the programmable items list for the currently selected option.
Scrolls forward through the programmable options list or choices for an the selected item.
Enables extended programming list so you can scroll through lists of items that have multiple
components such as, Zone 1 -30. See Section 4.1.2 for an example.
Accepts the entered data and scrolls up to the next menu item.
Used as shift key when entering special characters (A, B, C, D, or E characters). See Section
4.1.1 for more information.
Clear entry.
Operation/Description
to program items in this
4-1