GETTING OTHER INFORMATION AND PUBLICATIONS These publications can help you install the air FOR MORE INFORMATION, CONTACT conditioner or heat pump. You can usually find these THESE PUBLISHERS: at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
NOTE: All values can be changed + 10% via the + adjustment dip switches on the tap select control inclusive in the GTB1-A Blower Section (see instructions later in this manual, or on wiring diagram in blower section). TABLE 2 — FLOW RATES FOR VARIOUS FLUIDS...
BLOWER LINE POWER CONNECTION BLOWER CONVERSION FROM UPFLOW TO COUNTERFLOW OR HORIZONTAL Power connections for the GTB1-A can be made two RIGHT DISCHARGE different ways. Following the directions on Figure 3 for counterflow and The first is in “stacked” configurations, the blower can...
APPLICATION AND LOCATION GENERAL DUAL FUEL HEATING / COOLING Dual fuel is the combination of a fossil fuel furnace, normally The GT Series Geothermal Heat Pumps feature three sections gas or oil, with a heat pump. In milder weather the heat pump (GTA - Air Coil Section, GTB - Blower Section and GTC - uses the available outdoor warmth and will transport that heat Compressor Section) which cover upflow (bottom, right/left-...
CAUTION NEVER OPERATE MORE THAN 10KW STRIP HEAT WITH GEOTHERMAL HEAT PUMP OPERATIONAL. USE ADDITIONAL KW STRIP HEAT BEYOND 10KW ONLY IN EMERGENCY HEAT MODE. TABLE 5 ELECTRICAL HEAT SPECIFICATIONS Maximum Field Minimum 240 Volts 208 Volts For Use Heater Heater HACR Wire...
AIR FILTER APPLICATIONS FIGURE 5A FIGURE 5B COUNTERFLOW UPFLOW CENTRAL RETURN GRILLE(S) CENTRAL RETURN GRILLE(S) (ONE OR MULTIPLE) (ONE OR MULTIPLE) AIRFLOW AIRFLOW AIRFLOW AIRFLOW "A" FILTER SINGLE FILTER "V" FILTER CONFIGURATION CONFIGURATION CONFIGURATION AIR FILTER *NOTE: SINGLE FILTER MAY REQUIRE A TRANSITION FOR ADEQUATE FILTER SIZING.
WIRING INSTRUCTIONS GENERAL TABLE 7 CONTROL CIRCUIT WIRING All wiring must be installed in accordance with the National Electrical Code and local codes. In Canada, all Rated VA of Transformer Maximum Total wiring must be installed in accordance with the Canadian Control Circuit Secondary Distance of Control...
GROUND LOOP (EARTH COUPLED WATER LOOP APPLICATIONS) Most household water systems have more than enough NOTE: water pressure either from the well pump of the municipal Unit shipped from factory with 75 PSIG low pressure water system to overcome the pressure of head loss in 1/2 switch wired into control circuit and must be rewired to 55 inch or 3/4 inch household plumbing.
START UP PROCEDURE FOR GROUND 8. Start the unit in cooling mode by moving the thermostat LOOP SYSTEM switch to cool. Fan should be set for AUTO. 9. Check the system refrigerant pressures against the 1. Be sure main power to the unit is OFF at disconnect. cooling refrigerant pressure table in the installation 2.
FIGURE 8 FIGURE 8 Thermometer Thermometer NOTE: Slide retaining cap back to expose Dial face pressure guage double o-rings. Apply petroleum jelly to o-rings with guage adaptor NOTE: Slide retaining cap back to expose Dial face pressure guage to prevent damage and aid in insertion double o-rings.
GROUND WATER (WELL SYSTEM APPLICATIONS) Strainer (8) installed upstream of water coil inlet to collect NOTE: foreign material which would clog the flow valve orifice. Unit shipped from factory with 60 PSIG low pressure The figure shows the use of shutoff valves (4) and (5), on switch wired into control circuit for ground water the in and out water lines to permit isolation of the unit from applications.
the piping is not undersized, which would create too much The pressure requirements put on the pump are directly pressure due to friction loss. High pressure losses due to affected by the diameter of pipe being used, as well as, undersized pipe will reduce efficiency and require larger by the water flow rate through the pipe.
SYSTEM START UP PROCEDURE FOR WATER CORROSION GROUND WATER APPLICATIONS Two concerns will immediately come to light when 1. Be sure main power to the unit is OFF at disconnect. considering a water source heat pump, whether for ground water or for a ground loop application: Will there be 2.
4. Scale Formation. Of all the water problems, the LAKE AND POND INSTALLATIONS formation of scale by ground water is by far the most Lakes and ponds can provide a low cost source of water common. Usually this scale is due to the formation of for heating and cooling with a ground water heat pump.
C. If possible, use a submersible pump suspended in the J. The drain line should be installed with a slope of 2 dry well casing. Jet pumps and other types of suction inches per 10 feet of run to provide complete drainage pumps normally consume more electrical energy than of the line when the ground water heat pump is not similarly sized submersible pumps.
DESUPERHEATER DESCRIPTION INSTALLATION PROCEDURE – GENERAL The system is designed to heat domestic water using heat recovered from a water source unit’s hot discharge gas. Before beginning the installation, turn off all power supplies to the water heater and unit, and shut off the main water LOCATION supply line.
DESUPERHEATER OPERATION OF THE HEAT RECOVERY START UP AND CHECK OUT UNIT Be sure all shut off valves are open and all power supplies are on. Open a hot water faucet to permit any air to bleed The pump module is a very simple device containing basic controls and a circulating pump.
FIGURE 14 WIRING DIAGRAM COMPRESSOR CONTACTOR SIGNAL FROM GEOTHERMAL LOGIC CONTROL GTC LOW VOLTAGE DESUPERHEATER TERMINAL STRIP PUMP CONTROL BLACK CONTROL BLACK LOGIC THERMISTOR BLACK BLACK BLACK THERMISTOR BLACK OVER TEMP. LIMIT LINE VOLTAGE DESUPERHEATER PUMP PLUG MIS-2844 PUMP MOTOR BI-METAL TEMPERATURE LIMIT...
1.) If temperature difference is greater than 3°F, DESUPERHEATER CONTROL BOARD SEQUENCE OF OPERATION then the control will continue to energize pump relay. The desuperheating control board will make a 2.) If temperature difference is less than 3°F, then determination whether or not to energize the pump the control will de-energize the pump relay.
SEQUENCE OF OPERATION BLOWER PART LOAD HEATING (No Electric Heat) When thermostat system is placed in HEAT, the reversing Blower functions are all controlled through 24 VAC input valve solenoid is no longer energized. On a call for part signals from the control thermostat and 208/230 VAC being load heating, the thermostat completes a call from “R”...
SEQUENCE OF OPERATION HIGH PRESSURE SWITCH UNDER & OVER VOLTAGE PROTECTION (TERMINALS HP1 & HP2) Circuit will be proved as When an under or over voltage condition exists, the “closed” prior to energizing “A” or “CC” terminals. If controller locks out the unit. When condition clears, the controller automatically releases the unit to normal pressure switch opens, compressor will go into soft lockout mode and compressor operation will be terminated;...
FIGURE 17 — COMPONENT LOCATION WATER COIL LOW PRESSURE SWITCHES REVERSING VALVE HIGH PRESSURE SWITCH EXPANSION VALVE DESUPERHEATER COIL LOW VOLTAGE FILTER/DRIER COMPRESSOR PUMP UNIT HIGH VOLTAGE PUMP MODULE HIGH VOLTAGE MIS-2838 FIGURE 18 — CONTROL PANEL TERMINAL STRIP GEOTHERMAL DESUPERHEATER LOGIC CONTROL CONTROL BOARD...
REFRIGERANT CHARGE LINE SET INSTALLATION – GTA COIL 3. Final torque should be achieved. Use the appropriate SECTIONS size wrench in conjunction with a second (backing) wrench to ensure that fittings do not spin or twist on CHARGE ADJUSTMENT the copper refrigerant lines. Use the following torque All supplied line sets with threaded refrigerant connections rates: are factory evacuated and charged with R-410A refrigerant...
REFRIGERANT CHARGE GENERAL – GTADP COIL SECTIONS DO NOT CONNECT THE LINE SET TO THE CONDENSER SECTION GENERAL (GTADP Add-On Coils) Pre-charge the line set and evaporator coil with the amount These instructions are intended as a general guide and do not of R-410A calculated earlier.
REFRIGERANT CHARGE These units require R-410A refrigerant and Polyol Ester. SAFETY PRACTICES: 1. Never mix R-410A with other refrigerants. GENERAL: 2. Use gloves and safety glasses, Polyol Ester oils can 1. Use separate service equipment to avoid cross be irritating to the skin, and liquid refrigerant will contamination of oil and refrigerants.
SERVICE COMPRESSOR SOLENOID SERVICE HINTS 1. Caution owner to maintain clean air filters at all times. (See Sequence of Operation on Pages 37 & 38 for function.) Also, not to needlessly close off supply and return air A nominal 24-volt direct current coil activates the internal compressor solenoid.
TROUBLESHOOTING GE ECM 2.3 MOTORS ™ CAUTION: Symptom Cause/Procedure Disconnect power from unit before removing or replacing • Noisy blower or cabinet • Check for loose blower housing, panels, etc. connectors, or servicing motor. To avoid electric shock from • High static creating high blower speed? - Check for air whistling through seams in the motor’s capacitors, disconnect power and wait at least 5 ducts, cabinets or panels...
TROUBLESHOOTING GE ECM MOTORS CONT’D. ™ 7. Verify that the replacement control is correct for your application. Replacing ECM Control Module Refer to the manufacturer’s authorized replacement list. USING THE To replace the control module for the GE variable-speed indoor blower motor you need to take the following steps: WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION.
GROUND SOURCE HEAT PUMP GROUND SOURCE HEAT PUMP PERFORMANCE REPORT PERFORMANCE REPORT This performance check report should be filled out by installer and retained with unit. This performance check report should be filled out by installer and retained with unit. DATE TAKEN BY: UNIT: Mfgr Model No. THERMOSTAT: Mfgr Model No. Person Reporting Company Reporting Installed By Date Installed...
Page 52
THE FOLLOWING INFORMATION IS NEEDED TO CHECK PERFORMANCE OF UNIT. THE FOLLOWING INFORMATION IS NEEDED TO CHECK PERFORMANCE OF UNIT. FLUID SIDE DATA Cooling ** Heating Entering fluid temperature Leaving fluid temperature Entering fluid pressure PSIG Leaving fluid pressure PSIG Pressure drop through coil PSIG Gallons per minute through the water coil...
208/230-60-1 4-PIN UNIT 5-PIN MOTOR POWER PLUG POWER PLUG Indoor Blower Motor BLACK MODEL GTC60S1 GTC48S1 GTC36S1 16-PIN BLOWER SWITCH # CONTROL PLUG 240V 208V CIRCUIT BREAKER ADJUSTMENT TAPS NONE "+10%" "-10%" NONE RED/WHITE BLACK/WHITE NOTE: SWITCH #4 MUST BE TURNED ON WHEN BLOWER IS CONVERTED TO COUNTERFLOW OR HORIZONTAL RIGHT DISCHARGE...
Need help?
Do you have a question about the GTB1-A and is the answer not in the manual?
Questions and answers