CONTENTS Start Up Procedure for Ground Water System ..21 Getting Other Informations and Publications ... 3 Water Corrosion .......... 21 & 22 General Information Remedies of Water Problems ....... 22 Water Source Nomenclature ........4 Lake and/or Pond Installations ..... 22 & 23 Heater Package Nomenclature .......
GETTING OTHER INFORMATION AND PUBLICATIONS These publications can help you install the air FOR MORE INFORMATION, CONTACT conditioner or heat pump. You can usually find these THESE PUBLISHERS: at your local library or purchase them directly from the publisher. Be sure to consult current edition of each ACCA Air Conditioning Contractors of America standard.
WATER SOURCE PRODUCT LINE NOMENCLATURE Black Revision C = Copper Water Coil E-Coated Level (Closed Loop) Air Coil Ground N = Cupronickel Source (Open Loop) Electrical 230/208V 1-Phase Vertical Step Capacity 38 = Nominal heating capacity in thousands @ 50° water - Full Load Nominal cooling capacity in thousands @ 77°...
APPLICATION AND LOCATION GENERAL on the opposite side of the unit. (See Figure 2.) The two (2) access doors from the right hand return can be Units are shipped completely assembled and internally transferred to the left-hand return side and the one (1) wired, requiring only duct connections, thermostat left-hand panel can be transferred to the right hand wiring, 230/208 volt AC power wiring, and water...
FIGURE 2 FIELD CONVERSION TO LEFT-HAND RETURN Panel removed for clarity. Does not need removed to change control panel location. MIS-2617 1. Remove control panel fill plate. 2. Remove two screws securing control panel to unit. 3. Pass control panel through blower section rotating 180°. 4.
FILTER CONDENSATE DRAIN This unit must not be operated without a filter. It Drain lines must be installed according to local comes equipped with 2" disposable filters, which plumbing codes. It is not recommended that any should be checked often and replaced if dirty. condensate drain line be connected to a sewer main.
FIGURE 4 CONDENSATE DRAIN & PIPING ACCESS TO UNIT Water in connection MIS-2619 Water out connection Condensate drain access (4) locations Desuperheater Pump module connections 1/2" I.D. copper stub Manual 2100-545E Page 13 of 38...
WIRING INSTRUCTIONS GENERAL TABLE 6 CONTROL CIRCUIT WIRING All wiring must be installed in accordance with the National Electrical Code and local codes. In Canada, Maximum Total Rated VA of Transformer all wiring must be installed in accordance with the Distance of Control Circuit Secondary FLA...
GROUND LOOP (EARTH COUPLED WATER LOOP APPLICATIONS) NOTE: pressure of head loss in 1/2 inch or 3/4 inch household plumbing. A closed loop earth coupled heat pump Unit shipped from factory with 60 PSIG low pressure system, however, is separated from the pressure of the switch wired into control circuit and must be household supply and relies on a small, low wattage rewired to 45 PSIG low pressure switch for ground...
START UP PROCEDURE FOR GROUND recheck the selection of the loop pump module model for sufficient capacity. If the module LOOP SYSTEM selection is correct, there is probably trapped air or 1. Be sure main power to the unit is OFF at a restriction in the piping circuit.
FIGURE 7 FIGURE 7 Thermometer Thermometer NOTE: Slide retaining cap back to expose Dial face pressure guage NOTE: Slide retaining cap back to expose Dial face pressure guage double o-rings. Apply petroleum jelly to o-rings with guage adaptor double o-rings. Apply petroleum jelly to o-rings with guage adaptor to prevent damage and aid in insertion to prevent damage and aid in insertion...
GROUND WATER (WELL SYSTEM APPLICATIONS) NOTE: Constant Flow Valve (3) provides correct flow of water to the unit regardless of variations in water pressure. It is highly recommended on ground water systems Observe the water flow direction indicated by the arrow (pump &...
The pressure requirements put on the pump are that the piping is not undersized, which would create directly affected by the diameter of pipe being used, too much pressure due to friction loss. High pressure as well as, by the water flow rate through the pipe. losses due to undersized pipe will reduce efficiency The worksheet included should guarantee that the and require larger pumps and could also create water...
SYSTEM START UP PROCEDURE FOR WATER CORROSION GROUND WATER APPLICATIONS Two concerns will immediately come to light when considering a water source heat pump, whether for 1. Be sure main power to the unit is OFF at disconnect. ground water or for a ground loop application: Will 2.
4. Scale Formation. Of all the water problems, the provide adequate filtration of the water to allow good performance of the ground water heat pump. formation of scale by ground water is by far the most common. Usually this scale is due to the The following is a list of recommendations to follow formation of calcium carbonate but magnesium when installing this type of system:...
C. If possible, use a submersible pump suspended in The drain line should be installed with a slope of the dry well casing. Jet pumps and other types of 2 inches per 10 feet of run to provide complete suction pumps normally consume more electrical drainage of the line when the ground water heat pump is not operating.
SEQUENCE OF OPERATION BLOWER PART LOAD HEATING (No Electric Heat) When thermostat system switch is placed in HEAT, the Blower functions are all automatic through the thermostat control. (See Table 1 for the specific reversing valve solenoid is no longer energized. On a airflows on each speed.) Motor control inputs are all call for part load heating, the thermostat completes 24 VAC with line power to motor being continuous.
SEQUENCE OF OPERATION PRESSURE SERVICE PORTS COMPRESSOR CONTROL MODULE High and low pressure service ports are installed on The compressor control module is an anti-short cycle/ all units so that the system operating pressures can be lockout timer with high and low pressure switch observed.
FIGURE 13 COMPONENT LOCATION LOW PRESSURE SWITCHES EXPANSION VALVE SUCTION SERVICE PORT DISCHARGE SERVICE PORT DESUPERHEAT COIL HIGH VOLTAGE IN FLOW CENTER POWER COMPRESSOR WATER COIL HIGH PRESSURE SWITCH REVERSING VALVE MIS-2625 FIGURE 14 CONTROL PANEL E. HEAT TERMINAL TERMINAL GROUND CIRCUIT TRANSFORMER...
SERVICE SERVICE HINTS COMPRESSOR SOLENOID 1. Caution owner to maintain clean air filters at all (See Sequence of Operation on Pages 24 & 25 for times. Also, not to needlessly close off supply and function.) A nominal 24-volt direct current coil return air registers.
TROUBLESHOOTING GE X13-SERIES ECM MOTORS If the Motor is Running plate. If higher than allowed, additional duct work is needed. 1. It is normal for the motor to rock back and forth TROUBLESHOOTING GE X13-SERIES ECM2.3 ™ MOTORS If the motor does not shut off at the end of the on start up.
TROUBLESHOOTING GE X13-SERIES ECM2.3 MOTORS ™ CONT’D. Model X13 Communication Diagnostics 2. Initiate a demand from the thermostat and check the voltage between the common and the The X13 motor is communicated through 24 VAC low appropriate motor terminal (1-5). (“G” input voltage (Thermostat Control Circuit Wiring).
ACCESSORIES ADD-ON GVDM-26 PUMP MODULE KIT INSTALLATION NOTE: This section applies only if a GVDM-26 Pump 1. Follow all local, state, and national codes applicable Module is added. Refer to GVDM-26 instructions for to the installation of the pump module kit. complete installation details.
Ground Source Heat Pump Performance Report Date: ____________________ Technician: __________________________________________ Company Reporting: ________________________ Contact Phone: ____________________________ Owner’s Name: ____________________________ Owner’s Address: ___________________________ 1. Model/Serial Numbers: (For 3‐Pc. Geo‐Trio system, include coil/compressor/blower information) Model Number(s): ______________________________________________________________ Serial Number(s): _______________________________________________________________ 2. Accessory Information: Thermostat Mfgr. _____________________ Model/Part Number: ___________________ Flow‐Center* Mfgr. _____________________ Model/Part Number: ___________________ *if applicable 3. Open‐Loop Water Source Information: Where/how is water discharged ___________________________________________________ 4. Closed‐Loop Water Source Information: Horizontal Trenches ...
Page 36
The following information is needed to verify performance of the system. Note: Before testing, disable desuperheater, auxiliary electric heat, and any ventilation equipment that may allow outdoor air into the system. Measurements should be taken after a minimum 10 min. run time to ensure “steady‐state” of operation. Temperature and pressure measurements should be taken with a single thermometer and pressure gauge to eliminate discrepancies between multiple devices. Fluid Data: Stg. Cool Stg. Cool Stg. Heat Stg. Heat 5. Entering Fluid Temperature °F __________ __________ __________ __________ 6. Leaving Fluid Temperature °F __________ __________ __________ __________ 7. Entering Fluid Pressure psi __________ __________ __________ __________ 8. Leaving Fluid Pressure psi __________ __________ __________ __________ 9. Pressure Drop through coil (psi) __________ ...
Page 38
Line 2 Line 1 230/208-60-1 Power Source Circuit Circuit Terminal Terminal Breaker Breaker Block Block Compressor Capacitor 4 Pin Plug for Indoor Blower Motor Transformer 24VAC High Pressure Control Compressor Emergency Contactor Heat Relay Comp. Low Pressure Control Control Module Blower Control 3 Pin Heater...
Need help?
Do you have a question about the GV27S2AA and is the answer not in the manual?
Questions and answers