OPERATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST 920-0074 Model: QWSERV For Use With Bard 2 Through 5 Ton QW*S Series Manual: 2100-533A Bard Manufacturing Company, Inc. Supersedes: 2100-533 Bryan, Ohio 43506 File: Volume II, Tab 14 Since 1914...Moving ahead, just as planned.
ELECTRICAL SPECIFICATIONS CONTROL REQUIREMENTS GENERAL DESCRIPTION The Energy Recovery Ventilator was designed to 1. Indoor blower motor must be run whenever the ERV provide energy efficient, cost effective ventilation to is run. meet I. A. Q. (Indoor Air Quality) requirements while 2.
QWSERV to operate anytime the blower is operational, you will need to install a jumper wire from “G” to “A”. If you prefer to use Bard 8403-056 controller to make the ventilation “on-demand”, there is a connection adjacent to the thermostat...
TABLE 3 WINTER HEATING PERFORMANCE — (INDOOR DESIGN CONDITIONS 70°F DB) . f f . f f . f f NOTE: Sensible performance only is shown for winter application. LEGEND VLT = Ventilation Load – Total HRS = Heat Recovery – Sensible VLS = Ventilation Load –...
FIGURE 2 BELT REPLACEMENT INSTRUCTIONS Belt Replacement Route (1) replacement belt Instructions in top groove of pulley. Route (1) replacement belt in bottom groove of pulley. If belts "squeak" or "chirp" lubricate lightly with LPS-1 or equivalent "dry film" lubricant. MIS-2166 Manual 2100-533A Page...
FIGURE 4 DISCONNECT & TAPE OFF WIRE DISCONNECT AND TAPE OFF FOR CO2 CONTROLLED VENTILATION MIS-2759 Manual 2100-533A Page 11 of 12...
Page 12
FIGURE 5 FIELD SET CO SENSOR JUMPERS QWSERV VENT PACKAGE CONTROLLER SETTING FOR 1000 PPM SW2SW1 MIS-2756 "SW2" SET TO ON "AN" SET TO VOLTAGE "SW1" SET TO ON "OUT" SET TO 20-100% Manual 2100-533A Page 12 of 12...