CONTENTS Getting Other Information and Publications Figures Figure 1 Wood Framed Installation ..... 4 Wall Sleeve General Information Shipping Damage ..........4 Figure 2 Application of Sealant to 2 x 6 Plate ..5 General ..............4 Figure 3 Application of Sealant to Flanges ..5 Installation Instructions Figure 4 Masonry Construction Installation ..
11 West Street, 13th Floor Air Conditioning Systems New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286 Installation Instruction Manual ..Bard/2100-288 ASHRAE American Society of Heating, Refrigerating & Air Conditioning Engineers, Inc. 1791 Tullie Circle, N.E. Atlanta, GA 30329-2305...
SHIPPING DAMAGE INSTALLATION – WOOD FRAMED WALLS Upon receipt of equipment, the carton should be checked For wood frame construction walls, the dimensions of for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier the opening must be 48 inches tall by 43 inches wide.
FIGURE 2 APPLICATION OF SEALANT TO 2 6 PLATE SLEEVE OPENING OUTSIDE WALL TREATED 2 X 6 BOTTOM SUPPORT AND SEAL PLATE APPLY CONSTRUCTION APPLY CONSTRUCTION ADHESIVE TO SEAL. ADHESIVE TO SEAL. APPLY CONSTRUCTION ADHESIVE TO SEAL. FRONT VIEW FIGURE 3 APPLICATION OF SEALANT TO FLANGES Manual 2100-319F...
The sleeve is then reinserted into the prepared opening INSTALLATION – MASONRY from the outside of the building. All of the mounting CONSTRUCTION WALLS flanges must contact the exterior wall. Check to see For masonry construction walls, the dimensions for the that there is enough sealant to make this joint opening will be 48-1/4 inches tall by 43-1/4 inches wide.
Page 7
sealant must be applied as required. The sleeve must be square in the opening. A slope is built into the bottom of the sleeve from the inside to the outside. This will allow anchored to the wall. All four mounting flanges must be fastened with two fasteners each to the outside wall.
INSTALLATION WITH 16" THICK WALLS INSTALLATION WITH 23" THICK WALLS When an application is required on a building with 16" wall, When an application is required on a building with 23" wall, a Wall Sleeve model number QWS48A-16 is required. a Wall Sleeve model number QWS48A-23 is required.
ACCESSORY ITEM drain of the QT . This system allows the QT unit to be installed or removed from the sleeve without The QCDS48 is a condensate disposal system for use on connecting or disconnecting the drain line. all QT models.
ATTACHMENT OF WALL SLEEVE TO To use this method, discard the two side mounting UNIT brackets. Remove the nuts and washers from the threaded studs and retain for use later. Remove the All Wall Sleeve Models covered in this manual are lower cabinet door and locate the mating holes in the equipped with two different methods to attach the QT rear of the cabinet.