DISTRIbUTION TUbE AND CONTROl DEVICES lOCATION OPTIONS
fIgURE 12 – Recommended Installation locations, Split System Application
CHOOSINg A DISTRIbUTION TUbE lOCATION
When installing a steam humidifier on a split system, there are three locations that can be used to mount the steam
distribution tube: the supply plenum (Location A), the return duct (Location B), or a supply branch (Location C) .
Note: Wherever distribution tube is installed, there must be a minimum of 4 .5" between top of tube and the duct
ceiling . Refer to figures 16 and 17 on page 23 .
location A is the best choice because:
• The distribution tube is humidifying 100% of the air, and
• The supply air temperature is typically warmer than the return air temperature, allowing for better absorption.
location b is the second choice because the distribution tube is humidifying 100% of the air, but the cooler
temperature of the return air requires more space for absorption .
location C should be the last choice because, in most cases, there is more than one branch off the supply air
plenum, and less than 100% of the air would be humidified in such a multi-branch system . However, if there is only
one branch, the location C would be considered equal to location A because the same reasons listed under
Location A would apply .
Choosing control device locations
• I nstall the high humidity limit switch (a recommended optional device) a minimum of 5' (1.5 m) downstream
of the distribution tube .
• Install the Automatic Steam Humidifier Control in the return air drop a minimum of 6" upstream of the distribution tube.
• Install the airflow proving switch in the supply air plenum.