Specification; Indoor Unit - LG AUUW243D Manual

Exploded view
Hide thumbs Also See for AUUW243D:
Table of Contents

Advertisement

1. Specification

Indoor Unit

Indoor Unit
Nominal Capacity
Cooling
(Min~Rating~Max)
Heating
Nominal Input
Cooling
(Min~Rating~Max)
Heating
Indoor Unit
Nominal Capacity
Cooling
(Min~Rating~Max)
Heating
Nominal Input
Cooling
(Min~Rating~Max)
Heating
Outdoor Unit
Indoor Unit
Compressor
Type
Refrigerant Charge
Charge*
Type
Fan
Discharge
Noise Level(H/L)
Sound Press,1m
Dimensions
W*H*D
Net Weight
Outdoor
Piping connections
Liquid
Gas
Power Supply Cable(Includes earth)
Interunit Cable(Includes earth)
Max. Piping Length/Elevation
Power Supply
Running Current
Cooling/Heating
Air Circulation
Additional Refrigerant Charge (Over 7.5m)
Operation Range
Cooling
Heating
Note:
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27°C(80.6°F) DB/19°C(66.2°F) WB
- Outdoor Temperature 35°C(95°F) DB/24°C(75.2°F) WB
Heating: - Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB
- Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Btu/h
Btu/h
kW
kW
Btu/h
Btu/h
kW
kW
g(oz)
Side/Top
dB(A)±3
mm (inch)
kg(lbs)
mm (inch)
mm (inch)
No.*AWG
No.*AWG
m(ft)
Ø,V,Hz
A
CMM(CFM)
g/m(oz/ft)
°C(°F)
°C(°F)
2. Wiring cable size must comply with the applicable local and national
code.
3. The specification may be subject to change without notic for purpose of
improvement.
- 2 -
ATNH243PLAD
24,000
26,000
2.40
2.50
APNH2433LAD
24,000
26,000
2.50
2.55
AUUW243D
Rotary
2000(70.6)
R410A
side
55
870*808*320(34.3*31.8*12.6)
60(132)
9.52 (3/8)
15.88 (5/8)
No.*12
No.*18
50(164)/30(98)
1, 208~230, 60
10.0/10.7
58(2048)
35(0.38)
-10(14) ~ 43(109.4)
-15(5) ~ 24(75.2)
LGE Internal Use Only