Connecting the cable between indoor unit and outdoor unit

Connect the cable to the Indoor unit.

Connect the cable to the indoor unit by connecting the wires to the terminals on the control board
individually according to the outdoor unit connection.
(Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the
indoor unit.)
• Cooling & Heating Models
Terminals on the indoor unit
Color of Wires
Color of Wires
Terminals on the outdoor unit
1(L)
• Cooling Only Models
Terminals on the indoor unit
Color of Wires
Color of Wires
Terminals on the outdoor unit
1(L)
• If a power plug is not to be used, provide a circuit
breaker between power source and the unit as
shown below.
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
3(L)
4(N)
5
6
BROWN BLUE
G/Y
WHITE BLACK
BROWN BLUE
G/Y
WHITE BLACK
2(N)
3(L)
4(N)
5
6
POWER INPUT
1(L)
2(N)
3
4
BROWN BLUE
G/Y
WHITE RED
WHITE RED
BROWN BLUE
G/Y
2(N)
3(L)
4(N)
5
6
POWER INPUT
Connecting the cable between indoor unit and outdoor unit
7
The power cord connected to the outdoor unit
should be complied with the following specifications
RED
(Rubber insulation, type H05RN-F approved by
HAR or SAA).
30k, 32k
RED
7
NORMAL
CROSS-SECTIONAL
AREA 2.5mm
The connecting cable connected to the indoor and
outdoor unit should be complied with the following
specifications (Rubber insulation, type H07RN-F
approved by HAR or SAA).
NORMAL
CROSS-SECTIONAL
AREA 0.75mm
Main power source
Air
Conditioner
- 23 -
CAUTION
36k, 38k
NORMAL
CROSS-SECTIONAL
2
AREA 3.5mm
NORMAL
CROSS-SECTIONAL
2
AREA 0.75mm
Circuit Breaker
Use a circuit breaker
or time delay fuse.
LGE Internal Use Only
2
2

Hide quick links: