F300 ELECTRONIC AIR CLEANER
Offsets
If the duct connection to the furnace in a side installation allows
less than 7 in. (178 mm) for mounting the air cleaner cabinet,
add an offset to the elbow. See Fig. 5.
TYPICAL USE OF DUCT OFFSET TO ALLOW
SPACE FOR ELECTRONIC AIR CLEANER.
LESS
THAN
7 in.
[178 mm]
1 TURNING VANES HELP DISTRIBUTE AIRFLOW EVENLY.
Fig. 5. Typical use of duct offset to allow space for
electronic air cleaner.

INSTALLATION

When Installing this Product...
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
WARNING
Electric Shock Hazard.
Can cause electrical shock or equipment damage.
Do not connect to power before installation is complete.
Unpack Electronic Air Cleaner
! Check that all components are included. The electronic air
cleaner is shipped assembled. The unit consists of a
galvanized steel cabinet, power supply with On-Off switch
and neon light, two electronic cells, two metal mesh
prefilters, two media postfilters (on select models), access
door and product data literature.
! Order W8600F (optional) including mounting hardware and
installation literature separately.
! Order W8600A (optional) including mounting hardware,
batteries, and literature separately.
68-0240EF-5
Clean Blower Compartment
! Remove and discard the existing furnace filter.
! Thoroughly clean the blower compartment.
! If possible, power vacuum the ductwork to remove
accumulated dust in an existing home, or construction dirt in
a new home. The electronic air cleaner cannot remove dust
that has settled in the blower compartment and distribution
ducts.
! Check the edges of the furnace fan blades for dirt buildup
and clean as necessary. The fan will not deliver the rated
cfm if the blades are dirty.
Fasten Cabinet To Furnace
OFFSET
NOTE: This procedure shows a side installation on a typical
AT LEAST
! Remove and set aside the access door, electronic cells
7 in.
1
metal mesh prefilters and media postfilters.
[178 mm]
! Align the cabinet with the return air opening.
! Create opening in furnace to match air cleaner cabinet
opening.
! Install a transition when the furnace and air cleaner
openings are different sizes. See Fig. 4.
M5627A
! Place blocks under the cabinet so the unit is firmly
supported and level. The 5/8 in. (16 mm) mounting foot on
the cabinet hinge plate provides the minimum clearance
required for the access door hinge.
! Attach the cabinet securely to the furnace. The unit can be
attached directly, as shown, or a starting collar can first be
fitted in the furnace opening. Either drill holes and fasten with
sheet metal screws or rivets, or use slip joints. See Fig. 6.
8
highboy furnace. You may need to alter the procedure
to fit your application.
Fig. 6. Fasten cabinet to furnace.
M20804