THE WIRELESS REMOTE SENSOR SYSTEM IS MADE UP OF ONE RECEIVER AND AT LEAST ONE
WIRELESS SENSOR.
Up to 8 Wireless Sensors may be used with 1 Receiver. (Unit ID #0 - 7)
The Receiver automatically averages all the temperatures it receives
from any and all Wireless Sensors, up to 8 on the same House Code as
the receiver, and reports the average to the thermostat.
The Receiver will only 'listen' to Wireless Sensors with the same House
Code as the Receiver, and will 'ignore' Sensors with different House
Codes than the Receiver.
There can be up to 16 Remote Sensor Systems in each installation.
If more than 1 Wireless Sensor is used with 1 Receiver, then all Sensors
and the Receiver must have the same House Code for proper operation.
If more than 1 Wireless Sensor is used with 1 Receiver, than each
Sensor must have a different Unit ID.
SUGGESTIONS FOR USE OF ONE WIRELESS REMOTE SENSOR:
To report the Outdoor Temperature when using a compatible Residential
thermostat. It is recommended to attach the Wireless Sensor to a North
facing wall where it will not be in direct sunlight or the spray of sprinklers.
To report the temperature of a room, such as that of a Baby's room when
using a compatible Residential thermostat.
To control to, or to read only, the temperature at the return duct when
using a
compatible Commercial thermostat.
To control the temperature in a space that is different from where the
compatible Commercial thermostat is located.
SUGGESTION FOR USE OF MULTIPLE WIRELESS REMOTE SENSORS:
To control to an average of more than one Wireless Sensor in a large
open space using a compatible Commercial thermostat. This type of
application would include large, open office areas.
Receiver Setup & Installation
1
Set the House Code jumpers on the Receiver
A
HC1
HC2
HC4
HC8
Example A
House Code
ID = 2
WIRELESS REMOTE SENSOR
LED's
Jumper
Location
B
HC1
HC2
HC4
HC8
Example B
House Code
ID = 6
(2 + 4 = 6)
WIRELESS REMOTE SENSOR
RECEIVER
2
Connect the Receiver to the Thermostat
The Receiver is put inside the wall behind
the thermostat with the antenna fully extended.
MODEL
P474-0401-1RF/REC
with Override button
MODEL P474-0401-1RF
3
HC1
2
HC2
HC4
1
HC8
0
MODEL P474-0401-1REC
3
HC1
2
HC2
HC4
1
HC8
0