PROTECTION
The charger has the following protections:
SHORT CIRCUIT SHUT DOWN
In case of a short circuit on the output side, the output of the charger will be shut down.
The Charging Indication LED (4) on the front panel will turn red (On the Remote Panel
(15), the red LED "I Phase" will light, the green LED "Power" will, however, remain
lighted). The charger will be latched in this shut down condition and will NOT recover
automatically even after the short circuit condition is removed. To reset, the AC input
power on / off switch (9) at the back of the unit has to be switched off and on again.
OVER LOAD CURRENT LIMITING
The current drawn by the load is automatically limited to a maximum of 45 A for SEC-
1245A (16 A to 18 A when in "Mute Mode") and 25 A for SEC-2425A (8 A to 10 A in
"Mute Mode"). If the load tries to draw a higher current than these limits, the output
voltage of the unit will start to drop. The unit will automatically recover when the
overload condition is removed
REVERSE BATTERY CONNECTION CUT OFF
The output is internally fused on the DC side – 2 x 30 A fuses for SEC-1245A and 2 X 20
A fuses for SEC-2425A. In case, the polarity of the battery connection is reversed, the
fuse(s) will blow. The Charging Indication LED (4) on the front panel will turn red (On
the Remote Panel (15), the red LED "I Phase" will light, the green LED "Power" will,
however, remain lighted). The fuse(s) will be required to be replaced for the unit to
function again
THERMAL OVERLOAD SHUTDOWN
!
Caution
Keep the charger in a well ventilated, cool and open area. Do not block the
vent holes on the sides or the discharge openings of the cooling fan
In case the fan fails or if the cooling is not adequate due to higher ambient temperature,
inadequate air circulation or blockage of air ventilation openings, the thermal sensor for
over-temperature protection will shut down the output voltage of the charger. The
Charging Indication LED (4) on the front panel will turn red (On the Remote Panel (15),
the red LED "I Phase" will light, the green LED "Power" will, however, remain lighted).
The charger will be latched in this shut down condition and will NOT reset automatically
even after the unit has cooled down. To reset, the AC input power on / off (9) switch at
again.
the back of the unit has to be switched off and on
PROTECTION AGAINST TRANSIENTS / SURGES IN THE AC INPUT
In a number of locations, the AC line input is not clean and may contain high voltage
transients / surges. To prevent damage to the internal components against these unwanted
high voltages, the charger uses MOV (Metal Oxide Varistor) for protection. If surge /
transient voltage higher than approximately 170 VAC appear in the AC input, the MOV
will conduct and will blow the AC side fuse.