System Defaults - Heatcraft Refrigeration Products BEACON II SMART CONTROLLER H-IM-80C Installation And Operation Manual

Heatcraft refrigeration products llc. home theater server - multi-room video controller user manual
Table of Contents

Advertisement

SYSTEM DEFAULTS

Following are factory defaults for the parameters which can be programmed in
the Beacon II Smart Controller. If the user does not select a setting for any of
the following parameters, the default will be used.
It is important the user set ALL parameters based of their needs.
PARAMETERS
Refrigerant
Box Temperature
Superheat
Smart Defrost
Defrost start times
Defrost Fail-safe time
Defrost End Temperature
Alarm High Temperature
Alarm Low Temperature
Alarm Time
Temperature Units
Clock setting
Test mode
Service mode
**When Smart Defrost is turned on, 8 defrost periods per day will automatically be
programmed. These will be at 12:00 am, 3:00 am, 6:00 am, 9:00 am, 12:00 pm, 3:00
pm, 6:00 pm, and 9:00 pm. Also, the defrost fail safe time will be set to 60 minutes,
and the defrost termination temperature will be set to 55 F. The user can change
these as needed for the application (for version 1.2).
System Defaults
CODE
AIR
REFTYP
R22
BOXTMP
35 F
SUPRHT
8 F
SMTDEF
N/A
DEF ST
9 AM/9 PM
DEFSAF
40 min
DEFTMP
45 F
ALR HI
50 F
ALR LO
30 F
ALRMIN
60 min
F / C
F
12 / 24H
12 H
TEST
Off
SERVIC
Off
15
ELECTRIC
R404A
-10 F
8 F
Off**
4 AM, 10 AM, 4 PM, 10 PM
30 min
(60 min. when Smart Defrost is On)
60 F
(55 F when Smart Defrost is On)
5 F
-15 F
60 min
F
12 H
Off
Off