Honeywell F76S Quick Manual page 2

F76s series water filter
Hide thumbs Also See for F76S:

Advertisement

F76S Water Filters
EFFICIENT CLEaN FOR DEMaNDING aPPLICaTIONS
Product Number
F76S1007
F76S1015
F76S1023
F76S1031
F76S1049
F76S1056
The F76 water filter comes standard with a 100 micron stainless steel screen. 20, 50
and 200 micron screen kits are available separately
Capacity in Gallons Per Minute (gpm)
Pressure Drop
(psi) Across Filter
1/2
1
8
2
12
3
14
4
16
5
18
15
32
Flow Volume for 15 sec backwash at 60 psi inlet
3.2
NOTE: C
is equal to capacity at 1 psi pressure drop.
v
MV876B1018 Control Minimizes Guesswork
Overview
The MV876B Automatic Backwash Control is available as an
accessory. This control is fitted to the drain valve and is programmed
by the user to automatically perform the backwash function according
to the desired interval. Sixteen field-selectable backwash intervals
(from every four minutes to once every three months) eliminate the
need for external timer. MV876 can also be manually activated to
initiate backwash.
Learn More
Call toll-free 1-800-328-5111,
e-mail info@honeywell.com,
or visit forwardthinking.honeywell.com.
Automation and Control Solutions
In the U.S.:
Honeywell
1985 Douglas Drive North
Golden Valley, MN 55422-3992
In Canada:
Honeywell Limited
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
www.honeywell.com
Size
Union Connection
1/2 in
Sweat and NPT threaded tailpieces
3/4 in
Sweat and NPT threaded tailpieces
1 in
Sweat and NPT threaded tailpieces
1-1/4 in
Sweat and NPT threaded tailpieces
1-1/2 in
NPT threaded tailpieces
2 in
NPT threaded tailpieces
Pipe Size (in.)
3/4
1
1-1/4
11
18
20
16
25
28
19
31
35
22
36
40
25
40
45
43
70
78
3.2
4.0
4.0
67-7469 PR
September 2010
© 2010 Honeywell International Inc.
a. F76S DURING NORMAL FLOW
1-1/2
2
26
30
36
42
44
51
51
59
57
66
99
114
4.7
4.7
MV876B Timer Selections
Program Value
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
b. F76S DURING BACKWASH CYCLE
SCREEN
BACKWASH
IMPELLER
ENLARGED
CROSS SECTION
Product Number
Bayonet mounted shaft of 24
Vac motor and timer replaces
ball valve manual control
MV876B1018
for automatic backwash at
preprogrammed intervals. 24V
transformer not included
Backwash Interval
4 minutes
8 minutes
16 minutes
32 minutes
1 hour
2 hours
4 hours
8 hours
17 hours
34 hours
3 days
6 days
11 days
23 days
45 days
3 months
ENLARGED
CROSS SECTION
DEBRIS AND
SEDIMENT
M17362
Description

Advertisement

loading

This manual is also suitable for:

F76s1007F76s1015F76s1023F76s1031F76s1049F76s1056