FK06 DialSet®
LOW LEAD PRESSURE REGULATING
FILTER COMBINATION
SAFETY GUIDELINES
1. Follow the installation instructions.
2. Use and install the appliance
• according to its intended use
• in good condition
• with due regard to safety and risk of danger,
according to local codes and standards.
3. Note that the appliance is exclusively for use in the
applications detailed in these installation instruc-
tions. Any other use will not be considered to comply
with requirements and would invalidate the war-
ranty.
4. Please take note that any assembly, commissioning,
servicing and adjustment work may only be carried
out by authorized persons.
5. Immediately rectify any malfunctions which may
influence safety.
DESCRIPTION OF FUNCTION
The filter combination integrates a pressure reducing
valve and a rinsable fine filter cartridge in one appliance.
32325382-001
During normal operation, water flows through the filter
mesh to the body outlet. To rinse the filter, the ball valve is
opened which discharges the dirt particles. A continous
supply of filtered water is available also during the rinse
cycle.
The integral pressure reducing valve functions on a
balanced force principle whereby the force exerted by a
diaphragm is balanced against the force of an adjustment
spring. The inlet pressure has no influence on opening or
closing of the valve. Inlet pressure fluctuation does not
therefore affect the outlet pressure.
APPLICATION
Medium: Water
Inlet pressure: 250 psi (17.24 bar)
Outlet pressure: 25–90 psi (1.5–6 bar)
The filter is constructed for drinking water installations. In
case of a process water application the filter has to be
M36611
proven individually.
TECHNICAL DATA
Installation position: horizontal with filter bowl downward
Operating pressure: 250 psi (17.24 bar)
Operating temperature: 104°F (40°C)
Connection size: 3/4", 1", 1-1/4"
SCOPE OF DELIVERY
The filter combination consists of:
• Housing with pressure gauge connections on both
sides
• Threaded or sweat connections, based on model
• Valve insert complete with diaphragm and valve seat
INSTALLATION INSTRUCTIONS
WARNING
Install indoors only. Do not use in applications
where UV radiation and solvent vapors are
present.
38-00059EFS-01

Advertisement

loading

Summary of Contents for Honeywell DialSet FK06

  • Page 1 FK06 DialSet® LOW LEAD PRESSURE REGULATING FILTER COMBINATION INSTALLATION INSTRUCTIONS During normal operation, water flows through the filter mesh to the body outlet. To rinse the filter, the ball valve is opened which discharges the dirt particles. A continous supply of filtered water is available also during the rinse cycle.