Pumping Down - Mitsubishi Electric MSY-A24NA Installation Manual

Split-type air conditioners
Hide thumbs Also See for MSY-A24NA:

Advertisement

5=1. REMOVING AND INSTALLING THE PANEL ASSEMBLY
Removal
procedure
1) Remove
the 3 screws which fix the panel
assembly.
2) Remove
the panel
assembly.
Be sure
to remove
its bottom
end first.
1
1
2
installation
procedure
1) Point the horizontal vane slightly downward.
(Fig. 1)
2) Attach the bottom of the front panel under the horizontal vane.
3) Fit in the top of the front panel.
4) Fit in the bottom of the front panel and tighten it using screws.
5) Push the section of the front panel marked by the arrows to close the front panel
securely.
5-2. REMOVING THE INDOOR UNIT
Remove the bottom of the indoor unit from the installation
plate.
1 ) Remove the front panel. (Refer to 5-1 )
2) Insert flat screwdrivers
into the square holes at the left and right bottom of the indoor
unit and push them up; the bottom of the indoor unit goes down and the hooks are
released.
"1 Remove the screw.
*2 Remove the tab of corner box from the indoor unit, and pull the corner box.
*3 Pull the indoor unit to remove.
5
3,_
4
Horizontal vane
Fig. 1
Fig. 2
Square hole
5-3. PUMPING DOWN
When relocating or disposing of the air conditioner,
pump down the system following the
procedure below so that no refrigerant is released into the atmosphere.
1) Connect
the gauge
manifold valve to the service port of the stop valve on the gas
pipe side of the outdoor unit.
2) Fully close the stop valve on the liquid pipe side of the outdoor unit.
3) Close the stop valve on the gas pipe side of the outdoor
unit almost completely
so
that it can be easily closed fully when the pressure gauge shows 0 MPa [Gauge]
(0
Ibf/in. 2 [0 kgf/cm2]).
4) Start the emergency
COOL operation.
To start the emergency
operation
in COOL mode, disconnect
the power supply plug
and/or turn off the breaker. After 15 seconds,
connect the power supply plug and/or
turn on the breaker, and then press the E.O. SW once. (The emergency
COOL op-
eration can be performed continuously
for up to 30 minutes.)
5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure
gauge shows 0.05 to 0 MPa [Gauge] (approx. 7.25 to 0 Ibf/in 2 [0.5 to 0 kgf/cm2]).
6) Stop the emergency
COOL operation.
Press the E.O. SW twice to stop the operation.