Advertisement

5=1. REMOVING AND INSTALLING THE PANEL
ASSEMBLY
Removal
procedure
t) Remove the two screws that attach the panel assembly.
2) Remove the panel assembly.
Be sure to remove its bottom end first.
Installation
procedure
t) Install the panel assembly following
the removal procedure in reverse.
2) Be sure to press the positions
as indicated by the arrows in order to attach the
assembly completely
to the unit.
5-2. REMOVING THE INDOOR UNIT
Remove the bottom of the indoor unit from the installation
plate.
When releasing the corner part, release both left and right bottom corner part of
indoor unit and pull it downward
and forward as shown in the figure on the right.
If the above method
cannot
be used
Remove the front panel. Then, insert hexagonal
wrenches
into the square holes on
the left and right sides of the unit and push them up as shown in the following figure.
The bottom of the indoor unit lowers and releases the hooks.
Square hobe
Lower 7//, )
5-3. PUMPING DOWN
When relocating or disposing of the air conditioner, pump down the system following
the procedure
below so that refrigerant
is not released into the atmosphere.
1) Connect the gauge manifold valve to the service port of the stop valve on the gas
pipe side of the outdoor unit.
2) Fully close the stop valve on the liquid pipe side of the outdoor unit.
3) Close the stop valve on the gas pipe side of the outdoor unit almost completely
so that it can be easily closed fully when the pressure gauge shows 0 MPa [Gauge]
(0 Ibf/in. 2 [0 kgf/cm2]).
4) Start the emergency
COOL operation.
To start the emergency
operation
in COOL mode, disconnect
the power supply
plug and/or turn off the breaker. After 15 seconds, connect the power supply plug
and/or turn on the breaker, and then press the E.O. SW once. (The emergency
COOL operation can be performed
continuously
for up to 30 minutes.)
5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure
gauge shows 0.05 to 0 MPa [Gauge] (approx. 7.25 to 0 Ibf/in 2 [0.5 to 0 kgf/cm2]).
6) Stop the emergency
COOL operation.
To stop operation,
press the E.O. SW several times until all LED lamps turn off.
Refer to operating instructions for details.
When pumping down the refrigerant,
stop the compressor
before discon-
necting the refrigerant
pipes. The compressor
may burst
if air etc. get into it.