Flare Connection; Pipe Connection - Mitsubishi Electric MSZ-GA24NA Installation Manual

Split-type air conditioners
Hide thumbs Also See for MSZ-GA24NA:
Table of Contents

Advertisement

3-1. CONNECTING WIRES FOR OUTDOOR UNIT
1) Remove the service panel.
2) Remove the conduit cover.
3) Attach the conduit connector
to conduit cover with lock nut then secure it against unit
with screws.
4) Connect ground wires of indoor/outdoor
unit connecting
wire (A) and power supply cord
(K) to the TB support.
5) Loosen the terminal screw, and attach indoor/outdoor
unit connecting
wire (A) from the
indoor unit correctly
on the terminal block. Attach the wire to the terminal block securely
so that its core cannot be seen, and no external force affects the connecting
section of
the terminal block.
6) Firmly tighten the terminal screws. After tightening,
verify that the wires are tightly fas-
tened.
7) Connect power supply cord (K).
8) Install the conduit cover.
9) Install the service panel securely.
5/8 in.
1-3/8
in.
I
_(15mm)
(35 ram)
wead
_
Power supply
cord (K)
Service
panel
Lock nut
Conduit cover
/
Connector
Power supply cord (K)
Indoor/outdoor unit
(A)
to conduit cover
Grounding
terminal
TB support
i
ake ground wire a little longer than oth-
ers. (More than 1-3/8 in. [35 mm])
For future
servicing,
leave some slack in
the connecting wires.
A inch (mm)
Tightening
torque
Nut
Pipe diameter
inch
Clutch
Clutch
Wing nut
ftolb
inch (mm)
(mm)
type tool
type tool
type tool
Nom
(kgf°cm)
for R410A
for R22
for R22
1/4
13.7 to
1/4 (6.35)
(17)
0.06 to
17.7
0.08
(1.5 to
3t8
2.0)
34.3 to
3/8 (9.52)
(22)
0.04 to
41.2
0 to 0.02
0.06
(O to 0.5)
(1 .O to
1/2
1.5)
49.0 to
o 1/2 (12.7)
(26)
0.08 to
56.4
0.10
(2.0 to
5/8
2.5)
73.5 to
o 5/8 (15.88)
(29)
78.4
10 to 13
(140 to
180)
25 to 30
(350 to
420)
36 to 42
(500 to
575)
54 to 58
(750 to
800)
3-2. FLARE CONNECTION
1) Cut the copper pipe as straight as possible with a pipe cutter.
(Fig. 1, 2)
2) Remove all burrs from the cut section of the pipe, ensuring that precautions are taken to
avoid getting metal shavings into the piping. (Fig. 3)
3) Remove flare nuts attached to indoor and outdoor units, then put them on pipe.
4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in the dimension
shown in the table.
Select A mm from the table according to the tool you use.
5) Check
• Compare the flared work with Fig. 6.
• If flare is defective,
cut offthe section and repeat procedure.
3-3. PIPE CONNECTION
Fasten flare nut with a torque wrench as specified in the table above.
• When fastened too tight, flare nut may eventually
break and cause refrigerant leakage.
Indoor
unit connection
Connect both liquid and gas piping to indoor unit.
° Apply a thin coat of refrigerant oil (J) on the seat surface of pipe.
• To connect, first align the center, then tighten the first 3 to 4 turns of flare nut.
°
Use tightening
torque table above as a guideline for indoor unit side joints, and tighten
using two wrenches.
Excessive tightening damages the flare section.
Outdoor
unit connection
Connect pipes to stop valve pipe joint of the outdoor unit following
the same procedure
detailed in Indoor unit connection.
For tightening,
use a torque wrench or spanner.
3-4. INSULATION
AND TAPING
1) Cover piping joints with pipe cover.
2) For outdoor unit side, insulate the piping, including valves.
3) Apply piping tape (G) starting from the connection
on the outdoor unit.
• When piping has to be installed through a ceiling, closet or where the temperature
and
humidity are high, use additional field-supplied
insulation to prevent condensation.
_
opper
pipe
Fig. 1
Good
No good
Tilted
Uneven Burred
Fig. 2
Copper pipe
pare reamer
Pipe cutter
Fig. 3
Ftaring tool
tutch type
Wing nut type
Fig. 4
Smooth all around
Inside is shin-
ing without any
/_
scratches.
Even ,ength _
-[_
_
all around
I
Fig. 6
A
Die /
_'_--
Copper prpe
Flare nut
"Nc;_. 5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Msy-ga24na

Table of Contents