About Advanced Operation - TOTALINE 1 For All Owner's Manual

Programmable digital thermostat
Hide thumbs Also See for 1 For All:
Table of Contents

Advertisement

About Advanced Features & Operation
2 STAGE OPERATION - The 2nd Stage of heat or cool is
turned on when (1) the 1st Stage has been on for a
minimum of two minutes, and (2) the temperature spread
from the setpoint is equal to or greater than: the setpoint
plus the deadband, plus 2 degrees.
Heating
2 degrees
2nd Stage
1st Stage
turn on
turn on
MINIMUM HEAT/COOL SETPOINT DIFFERENCE - The Heat
and Cool setpoints will not be allowed to come any closer
to each other than the value set in Advanced Setup step
# 7, on page 13. This minimum difference is enforced
during Auto changeover
Cooling
Dead
Dead
Band
Band
2 degrees
Heat
Cool
1st Stage
Setpoint
Setpoint
turn on
and Program On
operation.
Page 16
2nd Stage
turn on

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1 for all p474-1050

Table of Contents