RBI FUTERA FUSION SERIES Installation & Operation Manual page 4

Futera fusion series finned copper gas boilers (model mb) & water heaters (model mw)
Hide thumbs Also See for FUTERA FUSION SERIES:
Table of Contents

Advertisement

FUTERA FUSION INSTALLATION AND OPERATION INSTRUCTIONS
All Air From Inside The Building
If the Futera is to be located in a confined space, the
minimum clearances listed in Table 1 must be maintained
between it and any combustible construction. When installed
in a confi ned space without the intake air option, Figures
5, 6 and 7, two permanent openings communicating with
an additional room(s) are required. The combined volume
of these spaces must have suffi cient volume to meet the
criteria for an unconfi ned space. The total air requirements
of all gas utilization equipment, fi replaces, wood stoves or
any type of exhaust fan must be considered when making
this determination. Each opening must have a minimum
free area of 1 in
2
/1000 Btu/hr, 2200 mm
the total input rating of ALL gas utilization equipment in the
confined area. Each opening must be no less than
2
2
100 in
, 64,516 mm
in size. The upper opening must
be within 12 in, 305 mm of, but not less than 3 in,
76 mm from, the top of the enclosure. The bottom opening
must be within 12 in, 305 mm of, but not less than 3 in,
76 mm from, the bottom of the enclosure.
All Air From Outside The Building
When installed in a confi ned space without utilizing the
intake air option two permanent openings communicating
directly with, or by ducts to, the outdoors or spaces that
freely communicate with the outdoors must be present. The
upper opening must be within 12 in, 305 mm of, but not
less than 3 in, 76 mm from, the top of the enclosure. The
bottom opening must be within 12 in, 305 mm of, but not
less than 3 in, 76 mm from, the bottom of the enclosure.
Where directly communicating with the outdoors
or communicating with the outdoors through vertical
ducts, each opening shall have a minimum free area of
2
1 in
/4000 Btu/hr, 550 mm
of all of the equipment in the enclosure.
Where communicating with the outdoors through horizontal
ducts, each opening shall have a minimum free area of
2
1 in
/2000 Btu/hr, 1100 mm
of all of the equipment in the enclosure.
When ducts are used, they must have the same cross-
sectional area as the free area of the opening to which they
connect.
When calculating the free area necessary to meet the
make-up air requirements of the enclosure, consideration
must be given to the blockage effects of louvers, grills and
screens. Screens must have a minimum mesh size of
1/4 in, 6.4 mm. If the free area through a louver or grill is
not known, ducts should be sized per Table 2.
Canadian installations must comply with CSA B149.1 when
air supply is provided by natural air fl ow from the outdoors
for natural draft, partial fan-assisted, fan-assisted, or
power draft-assisted burners, there shall be a permanent
air supply opening(s) having a cross-sectional area of not
2
less than 1 in
per 7,000 Btuh (310 mm
and including 1 million Btuh, plus 1 in
(155 mm
2
per kW) in excess of 1 million Btuh.
2
/kW based on
2
/kW of the total input rating
2
/kW of the total input rating
2
per kW) up to
2
per 14,000 Btuh
Table 2 – Make-up Air Louver Sizing
Required Cross Sectional Area
Input
1/4 in 6.4 mm
(MBH)
Wire Screen
2
2
in
cm
500
125
806
750
187
1206
1000
250
1613
1250
313
2019
1500
375
2419
1750
437
2819
1999
500
3226
Intake Air Option – General Guidelines
This confi guration provides combustion air directly to the
boiler/water heater's air intake adapter using a dedicated
pipe when using the direct vent option. Combustion air can
be drawn in horizontally through the same outside wall
which terminates the exhaust gases or vertically through
the roof, see Figures 1, 2, 3 & 4.
WARNING: Common intake air systems may be
used provided the common duct is sized properly.
An intake combustion air damper should be
installed if the common vent option is used in the
intake air pipe of each heater. Improper installation
can result in excessive levels of carbon monoxide
which can cause severe personal injury or death!
Single wall galvanized smoke pipe, single wall aluminum
pipe, fl exible aluminum pipe, PVC or CPVC pipe can be
used for the intake air pipe. It must be sized per Table 3.
Table 3 - Intake Air Pipe Sizing
Model
For Vertical
Size
(Up to 60')
in
500
8
750
8
1000
8
1250
10
1500
10
1750
12
2000
12
All joints in metal intake air systems must be secured using
corrosion resistant fasteners and sealed using a suitable
Silicone caulk. If PVC or CPVC is used, the joints must be
cleaned with a suitable solvent and connected using a
solvent based PVC cement. The combustion air system
MUST be supported by the building structure not the
boiler/water heater.
4
75% Free Area
25% Free Area
Metal Louvers
Wooden Louvers
2
2
2
in
cm
in
cm
167
1077
500
250
1613
750
333
2148
1000
416
2684
1250
500
3226
1500
583
3761
1750 11,290
667
4303
2000 12,900
For Horizontal
(Up To 60')
mm
in
mm
203
6
152
203
6
152
203
6
152
254
8
203
254
10
254
305
12
305
305
12
305
2
3226
4839
6452
8065
9677

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents