II
Advanced Setup
Note: Set the thermostat to 'OFF' mode before adjusting settings.
FAN
Press the Fan button
for 10 seconds to enter
these Setup screens.
This step only appears in compressor equipped systems.
Select the cycles per
hour limit.
d=cycles per hour
limit defeated.
(d, 2 - 6)
Default = 6 cycles / hour
Adjust the deadband
from 1 - 6 degrees F.
Deadband is the difference
between Room temperature
& setpoint before the
equipment will turn on.
Default = 2 degrees
Adjust the minimum
temperature setpoint
that is used when the
thermostat indicates OFF.
Heat will come on when the
temperature falls below this
setpoint.
Default = 60 degrees
The purpose of d1 is to allow the installing technician
to override the thermostats 5 minute compressor lockout.
After installation is complete this setting should be set between
d and 6 cycles per hour.
This feature prevents rooms from getting to hot or too cold
when heating or cooling is turned off.
INSTALLATION
NOTE: Each step's description is
located at
corner of the
easy reference.
CYCLES/HOUR
6
TO SET PRESS,
OR
2
DEADBAND
TO SET PRESS,
OR
60
OFF MIN
SETPOINT
TO SET PRESS,
OR
Continued
Page 6
the top right
display for
Press
FAN
Press
FAN
Press
FAN