What You Will See And Hear With This Alarm; Installation; Where To Install This Alarm; Where This Alarm Should Not Be Installed - First Alert SCO7 User Manual

Combination carbon monoxide & smoke alarm with voice & location and remote control test/silence

Advertisement

WHAT YOU WILL SEE AND HEAR WITH THIS ALARM

Under Normal Operations
Voice: Silent
Horn: Silent
When You Test the Alarm
Voice: "Testing." "Warning, evacuate smoke in [Location, example:
"Kitchen"]. Evacuate."
Horn: 3 beeps, pause, 3 beeps, voice
Power/Smoke LED: Flashes Red
CO LED: Off
followed by
Voice: "Warning, evacuate carbon monoxide in [Location, example:
"Kitchen"]. Evacuate."
Horn: 4 beeps, pause, 4 beeps, voice
Power/Smoke LED: Off
CO LED: Flashes Red
If Battery Becomes Low or is Missing
Voice: "Replace battery in [Location, example "Kitchen"]." Repeated
every 5 hours
Horn: chirps once a minute
Power/Smoke LED: Flashes approximately once a minute
CO LED: Off
If Alarm is Not Operating Properly
Voice: "Detector error in [Location, example "Kitchen"], please see
manual." Repeated every 5 hours
Horn: Three rapid chirps every minute
Power/Smoke LED: Flashes approximately once a minute
CO LED: Off
Alarm Levels of CO are Detected
Voice: "Warning, evacuate carbon monoxide in [Location, example:
"Kitchen"]. Evacuate." "____ ppm."
Horn: 4 beeps, pause, 4 beeps, voice*
Power/Smoke LED: Off
CO LED: Flashes Red
*NOTE: If unit goes into CO alarm, the regular 4 beeps-brief pause cycle will
repeat for four minutes. After four minutes, the pause will increase to one minute.
Smoke is Detected
Voice: "Warning, evacuate smoke in [Location, example: "Kitchen"].
Evacuate."
Horn: 3 beeps, pause, 3 beeps, voice
Power/Smoke LED: Flashes Red
CO LED: Off
Smoke Alarm is Silenced
Voice: "Horn silenced. Detector
active."
Horn: Off
Power/Smoke LED: Flashes Red
CO LED: Off

INSTALLATION

WHERE TO INSTALL THIS ALARM

Minimum coverage for Smoke Alarms, as recommended by the National
Fire Protection Association (NFPA), is one Smoke Alarm on every floor, in
every sleeping area, and in every bedroom (See "Regulatory Information For
Smoke Alarms" for details on the NFPA recommendations).
For CO Alarms, the National Fire Protection Association (NFPA) recommends
that a CO Alarm should be centrally located outside of each separate sleeping
area in the immediate vicinity of the bedrooms. For added protection, install
additional CO Alarms in each separate bedroom, and on every level of your
home.
NOTE: For added protection, install an additional Smoke/CO Alarm at least
15 feet (4.6 meters) away from the furnace or fuel burning heat source where
possible. In smaller homes or in manufactured homes where this distance cannot
be maintained, install the Alarm as far away as possible from the furnace or
other fuel burning source. Installing the Alarm closer than 15 feet (4.6 meters) will
not harm the Alarm, but may increase the frequency of unwanted alarms.
In general, install combination Smoke and Carbon Monoxide Alarms:
On every level of your home, including finished attics and basements.
Inside every bedroom, especially if people sleep with the door partly or
completely closed.
In the hall near every sleeping area. If your home has multiple sleeping
areas, install a unit in each. If a hall is more than 40 feet (12 meters) long,
install a unit at each end.
At the top of first-to-second floor stairs.
At the bottom of the basement stairs.
For additional coverage, install Alarms in all rooms, halls, and storage
areas, where temperatures normally remain between 40˚ F and 100˚ F
(4˚ C and 38˚ C).
Power/Smoke LED: Flashes Green once a
minute
CO LED: Off
CO Alarm is Silenced
Voice: "Horn silenced. Detector
active."
Horn: Off
Power/Smoke LED: Off
CO LED: Flashes Red
Recommended Placement
SUGGESTED AREAS FOR INSTALLING
SMOKE ALARMS, CO ALARMS, AND COMBO UNITS
In new construction AC and AC/DC smoke alarms MUST
be interconnected to meet NFPA recommendations.
When installing on the wall, the top edge of Smoke Alarms should be
placed between 4 inches (102 mm) and 12 inches (305 mm) from the
wall/ceiling line.
When installing on the ceiling, place the alarm as close to the
center as possible.
In either case, install at least 4 inches (102 mm) from where the wall and
ceiling meet. See "Avoiding Dead Air Spaces" for more information.
NOTE: For any location, make sure no door or other obstruction could keep
carbon monoxide or smoke from reaching the Alarm.
Installing Smoke/CO Alarms in Mobile Homes
For minimum security install one Smoke/CO Alarm as close to each sleeping
area as possible. For more security, put one unit in each room. Many older
mobile homes (especially those built before 1978) have little or no insulation. If
your mobile home is not well insulated, or if you are unsure of the amount of
insulation, it is important to install units on inside walls only.

WHERE THIS ALARM SHOULD NOT BE INSTALLED

Do NOT locate this Smoke/CO Alarm:
In a location where it could be easily triggered when using your remote to
operate your TV, VCR, etc.
In garages, furnace rooms, crawl spaces and unfinished attics. Avoid
extremely dusty, dirty or greasy areas.
Where combustion particles are produced. Combustion particles form
when something burns. Areas to avoid include poorly ventilated kitchens,
garages, and furnace rooms. Keep units at least 20 feet (6 meters) from
the sources of combustion particles (stove, furnace, water heater, space
heater) if possible. In areas where a 20-foot (6 meter) distance is not
possible – in modular, mobile, or smaller homes, for example – it is
recommended the Smoke Alarm be placed as far from these fuel-burning
sources as possible. The placement recommendations are intended to
keep these Alarms at a reasonable distance from a fuel-burning source,
and thus reduce "unwanted" alarms. Unwanted alarms can occur if a
Smoke Alarm is placed directly next to a fuel-burning source. Ventilate
these areas as much as possible.
Within 5 feet (1.5 meters) of any cooking appliance. In air streams near
kitchens. Air currents can draw cooking smoke into the smoke sensor and
cause unwanted alarms.
In extremely humid areas. This Alarm should be at least 10 feet (3 meters)
from a shower, sauna, humidifier, vaporizer, dishwasher, laundry room,
utility room, or other source of high humidity.
In direct sunlight.
In turbulent air, like near ceiling fans or open windows. Blowing air may
prevent CO or smoke from reaching the sensors.
In areas where temperature is colder than 40˚F (4˚C) or hotter than 100˚F
(38˚C). These areas include non-airconditioned crawl spaces, unfinished
attics, uninsulated or poorly insulated ceilings, porches, and garages.
In insect infested areas. Insects can clog the openings to the sensing
chamber.
Less than 12 inches (305 mm) away from fluorescent lights. Electrical
"noise" can interfere with the sensor.
In "dead air" spaces. See "Avoiding Dead Air Spaces".
AVOIDING DEAD AIR SPACES
"Dead air" spaces may prevent smoke from reaching the Smoke/CO Alarm. To
avoid dead air spaces, follow installation recommendations below.
On ceilings, install Smoke/CO Alarms as close to the center of the ceiling as
possible. If this is not possible, install the Smoke/CO Alarm at least 4 inches
(102 mm) from the wall or corner.
For wall mounting (if allowed by building codes), the top edge of Smoke/CO
Alarms should be placed between 4 inches (102 mm) and 12 inches (305 mm)
from the wall/ceiling line, below typical "dead air" spaces.
On a peaked, gabled, or cathedral ceiling, install first Smoke/CO Alarm
within 3 feet (0.9 meters) of the peak of the ceiling, measured horizontally.
Additional Smoke/CO Alarms may be required depending on the length, angle,
etc. of the ceiling's slope. Refer to NFPA 72 for details on requirements for
sloped or peaked ceilings.
2
KEY:
SMOKE ALARMS
SMOKE ALARM WITH
SILENCE FEATURE
CO ALARMS
BOTH, OR COMBINATION
SMOKE/CO ALARMS
Suggested locations are based on
NFPA recommendations (NFPA 72
for Smoke Alarms and NFPA 720 for
Carbon Monoxide Alarms). Always
refer to national and local codes
before beginning any installation.