Mitsubishi FX 2N-20PSU DC User Manual page 7

Dc power supply unit
Table of Contents

Advertisement

FX
-20PSU DC POWER SUPPLY UNIT
2N
USER'S MANUAL
This manual contains text, diagrams and explanations which will guide the reader in the correct installation
and operation of the FX
-20PSU DC power supply unit. It should be read and understood before
2N
attempting to install or use the unit. Further information can be found in the FX series PLC hardware man-
uals.
If in doubt at any stage during the installation of the FX
-20PSU DC power supply unit always consult a
2N
professional electrical engineer who is qualified and trained to the local and national standards.
Note's on the symbology used in this manual
At various times through out this manual certain symbols will be used to highlight points of infor-
mation which are intended to ensure the users personal safety and protect the integrity of the
equipment. Whenever any of the following symbols are encountered, its associated note must be
read and understood. Each of the symbols used will now be listed with a brief description of its
meaning.
Hardware warnings
1) Indicates that the identified danger WILL cause physical and property damage.
2) Indicates that the identified danger could POSSIBLY cause physical and property damage.
Guidelines for the safety of the user and protection of the FX
POWER SUPPLY UNIT
This manual has been written to be used by trained and competent personnel. This is defined
by the European directives for machinery, low voltage and EMC.
If in doubt at any stage during the installation of the FX
sional electrical engineer who is qualified and trained to the local and national standards. If in
doubt about the operation or use of the FX
-20PSU please consult the nearest Mitsubishi
2N
Electric distributor.
Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential
damage that may arise as a result of the installation or use of this equipment.
All examples and diagrams shown in this manual are intended only as an aid to understand-
ing the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for
actual use of the product based on these illustrative examples.
Owing to the very great variety in possible application of this equipment, you must satisfy
yourself as to its suitability for your specific application.
1. INTRODUCTION
The DC power supply unit FX
-20PSU is available as the following applications.
2N
Power supply of 24V DC power type PLC
Power supply of special extension block of PLC
Power supply of sensor connected to input of PLC
Power supply of DC load connected to output of PLC
Power supply of display unit such as graphic operation terminal (GOT)
2. EXTERNAL DIMENSION
f
JY992D85101B
3. GENERAL SPECIFICATIONS
Item
-20PSU DC
2N
Operating Tempera-
ture
Storage Temperature
Operating Humidity
-20PSU always consult a profes-
2N
storage Humidity
Vibration Resistance
- Direct Mounting
Vibration Resistance
- DIN rail Mounting
Shock Resistance
Noise Immunity
Dielectric Withstand
Voltage
Insulation Resistance
Ground
PLC/power
supply
Dedicated grounding
(best)
Description
0 to 55 °C (32 to 131 °F)
-20 to 70 °C (-4 to 158 °F)
35 to 85% Relative Humidity, No condensation
35 to 90% Relative Humidity, No condensation
10 - 57 Hz: 0.75 mm Half Amplitude
2
57 - 150 Hz: 9.8 m/s
Acceleration
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
10 - 57 Hz: 0.035 mm Half Amplitude
2
57 - 150 Hz: 4.9 m/s
Acceleration
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
2
147m/s
Acceleration, Action Time: 11 ms
3 times in each direction X, Y, and Z
1000Vp-p, 1microsecond, 30 - 100 Hz, tested by noise simulator
500V AC > 1 min, tested between all points, terminals and ground
5MΩ > at 500V DC, tested between all points, terminals and ground
Class 3 (100 Ω or less)
Another
PLC/power
Another
PLC/power
equipment
supply
equipment
supply
Common grounding
Common grounding
(good)
(not allowed)
4. PERFORMANCE SPECOFOCATIONS
Input voltage
85 to 264V AC
Frequency
50/60Hz
Input
Fuse rating
3.15A (built in)
Rush current
60A/200V AC maximum
Output voltage
24V DC ± 10%
2A (maximum), 0.2A (minimum)
Output current
(Derating is performed if ambient temperature exceeds 40 °C.)*1
Output
Ripple noise
500mVp-p or less
Holding time
10ms/100V AC
Protection against
Actuated when current becomes 110 - 160% or more, voltage drop
overcurrent *2
occurs automatic recovery
Protection
function
Protection against
Actuated when voltage becomes 110 - 140% or more, output shuts-
overvoltage *3
down, no automatic recovery (diode clamp)
Output indication
Green LED(POWER) is lit while voltage is output.
Serial/parallel operation with other power supply units is not allowed.
Others
(See Section 6.3)
[Output derating]
100
80
60
40
20
0
0
10
20
30
40
Ambient temperature (°C)
*1 The available output current varies depending on the ambient operating temperature. Use the FX
20PSU in the available range in accordance with the output derating graph shown above.
*2 If the output current flows beyond the specified value, the overcurrent protection circuit is actuated
and the output voltage drops.
When the overcurrent status or the short-circuit status returns to acceptable levels, the output voltage
automatically recovers.
*3 If the voltage beyond the specified value is generated by an internal failure, etc., the output is shut
down so that high voltage is not output. When the voltage comes from a load circuit connected to an
output terminal or when overvoltage is input from the outside, the overvoltage protection circuit may
be actuated.
When the overvoltage protection circuit is actuated, the output is shut down and does not automati-
cally recover. Ask for inspection and repair after such an occurance.