Generator Restraint; Generator Compartments; Compartment Size; Compartment Construction - Generac Power Systems 009600-5, 009734-5 Owner's Manual

Air-cooled recreational vehicle generators
Table of Contents

Advertisement

• Protect the generator against road splash and debris.
Baffles or splash guards may be required to protect cer-
tain areas of the generator. To make sure the generator
is adequately protected, road test the installation
through mud, water and slush.
Figure 6.2 – Typical Suspended Mounting System
• The installer must make certain that the selected
location will permit adequate cooling and ventilating
airflow to be supplied.
N

6.1.4 GENERATOR RESTRAINT

Use four 3/8"-16 hardened steel bolts (Grade 5) to fasten
the generator to the supporting frame or the support tub-
ing. These bolts must pass through (a) the generator
mounting base, (b) the compartment floor (if a compart-
ment is used) and (c) the supporting framework
(Figure 6.3). All bolts must be long enough so that when
tight, at least three threads are visible past the retaining
lock nuts. Refer to Section 6.2 for the location of the gen-
erator mounting holes.
Figure 6.3 – Typical Generator Restraint
6.2

GENERATOR COMPARTMENTS

Whether the generator set is being installed inside a com-
partment specifically manufactured to house a generator
or inside a compartment that the installer constructs, the
compartment MUST meet certain specifications as out-
lined in the following sections:
N

6.2.1 COMPARTMENT SIZE

Plan the compartment size carefully. Provide a mini-
mum clearance of 1/2 inch (13 mm) on the front and
top, 1 inch (25 mm) on the sides, and 1/2 inch (13 mm)
PRIMEPACT 66G and 66LP Recreational Vehicle Generators
from the back for air circulation AFTER the compart-
ment has been lined with metal and sound insulation
(Figure 6.4).
Refer to "Figure 5.2 – Major Features and
Dimensions" on Page 21.
N
• The generator compartment should be either con-
structed of, or lined with, 26-gauge galvanized steel.
Aluminum
to
melting point.
• If the compartment is lined with galvanized steel, it
may be constructed of any material. Generac recom-
mends that the compartment be constructed of 1/2-
inch thick plywood (not strandboard), with the floor
made of a double thickness of 1/2-inch plywood with
the grain of the wood at cross section for added
strength (Figure 6.5).
Figure 6.5 – Typical Compartment Construction
Section 6 – Installation
NOTE:
Figure 6.4 – Clearances
Plywood
Compartment
1 1/2" Clearance on Top
1/2"
Insulation
in Front

6.2.2 COMPARTMENT CONSTRUCTION

NOTE:
is
NOT
an
galvanized
steel
due
Generac
®
1" Clearance
in Back
1" Each Side
acceptable
alternative
to
aluminum's
Power Systems, Inc. 23