• A Certified AC power (mains) disconnect or circuit breaker should be mounted near the SafeGuard Controller and installed following applicable local and national codes. If a switch is used instead of a circuit breaker, a properly rate CERTIFIED fuse or current limiter is required to installed as per local or national codes.
System configuration is through user friendly menus and all configuration data is retained in non-volatile memory during power interruptions. The SafeGuard Controller’s front panel is shown below in Figure 1.0 displaying the 8 channel bar graph screen. Additional data screens are shown in Figure 2.0.
1.1.1 TREND SCREEN The SafeGuard Controller’s Trend screen shown in Figure 2.0 displays a 24 hour trend of input data for the channel selected. Horizontal tic marks are each hour and vertical tic marks are each 10% of full scale. Dashed lines indicate alarm levels. The graphic LCD is 240 pixels wide so each pixel represents 1/10 hour, or 6 minutes worth of data.
1.2 SPECIFICATIONS: 1.2.1 DC POWER SUPPLY REQUIREMENTS Standard SafeGuard Controller power requirements are 10-30VDC @ 3 watts applied to terminals 9 & 11 of TB2 on the standard I/O PCB (see section 3.0). Optional features increase power consumption as described below: •...
SECTION 2 2.0 BASIC OPERATION The SafeGuard Controller offers 3 graphic screens for viewing monitored data and a Set- Up menu screen for operator interface to configuration menus. They are shown below in Figure 2.0. The Bar Graphs screen allows viewing of all active channels simultaneously.
Figure 2.0 2.1 SETUP MENU CONFIGURATION Variables inside system and channel menu trees allow optimum SafeGuard Controller configuration for a wide range of demanding multi-point monitoring applications. Access to menus is via the Setup mode by pressing EDIT and activating the Setup screen shown in Figure 2.0.
2.2 CHANNEL CONFIGURATION MENUS Figure 2.1 illustrates the menu tree for configuring Channel variables. These items affect only the specific channel selected. System specific variables are in the menu tree shown in section 2.3. Figure 2.1 SafeGuard Controller User Manual MAN-0115 Rev 0...
(see section 2.3.3). Discrete LED indicators on the front panel indicate the status of each alarm and relay. Any new alarm event causes the associated LED to flash until Alarm Reset occurs SafeGuard Controller User Manual MAN-0115 Rev 0...
• The Modbus RS-485 master port connected to modbus slave devices. Note: Each Modbus menu selection also requests the RTU # and the Alias register # location of the data to be retrieved from the RTU. Alias register SafeGuard Controller User Manual MAN-0115 Rev 0...
SafeGuard Controller, select Analog Input with Local Cal. Note that gas sensors are not connected directly to the SafeGuard Controller at this time, hence Sensor Direct is not used.
(1.5mA is -15.62% of full scale when 4-20mA is the range). • It should be noted that for Net Safety Flame Detectors the current output for a visual integrity fault is 2.0 mA this corresponds to a Marker % of -12.5%. For Net Safety Gas Sensor Fault Condition, the current output is 2.5 mA which...
Sensor Life. Sensor Life is stored in the SafeGuard Controller’s modbus database and displayed as a bar-graph in the Sensor Info screen (see section 2.3.6). It is a useful tool for planning sensor replacement schedules.
SafeGuard Controller may be set for 8 channel mode, deactivating channels 9-16. This is done in the System Setup menu described in section 2.3. The SafeGuard Controller will only allow 15 channels to be turned off. At least one channel must remain on.
2.2.7 CAL MODE This SafeGuard Controller feature is only accessible when Sensor Direct or Analog Input with Local Cal. is selected. The Analog Input with Local Cal. option may be used if the transmitter and sensor connected to the controller are located in an area not easily accessible.
Some items needing configuration are not specific to a channel but affect the entire SafeGuard Controller system. These are located in the system entry menu shown on the left side of Figure 2.9. System menus are accessed by pointing to the desired item and pressing EDIT.
SafeGuard Controller. In these cases, it may be undesirable for a detector on channel 9 to trip the same relay as a detector on channel 2. The Group menus may restrict this.
2.3.3 COMMON HORN RELAY & LOCAL PIEZO The SafeGuard Controller is equipped with a low decibel audible piezo which chirps when keys are pressed and may be configured to audibly indicate alarm conditions. The common horn relay is similar to the common A1 & A2 common relays.
ID settings are per channel as described in section 2.2.4). This slave port may be used to transfer the SafeGuard Controller data to a host device such as a PC, PLC, DCS or even another SafeGuard Controller. The slave port is addressable, allowing many SafeGuard Controllers to be connected to a single RS-485 cable.
If 8 channels are selected by this menu they are channels 1-8 and 9-16 are disabled. One way the SafeGuard Controller cost is kept low is Input / Output option PCB’s are arranged into groups of 8 channels. Therefore, users with less than 9 channels require only 1 PCB and do not pay for I/O hardware for 16 channels.
It is very important to record the 4 digit code. However, if lost it may be displayed briefly at power up using the following procedure: Remove power from the SafeGuard Controller. Reapply power and as the alarm LED's begin scrolling down, hold the following keys simultaneously "UP", "DOWN", "NEXT", &...
SECTION 3 MAIN I/O INTERFACE PCB The most basic SafeGuard Controller requires only the I/O PCB shown in Figure 3.1 for interfacing to field wiring. The SafeGuard Controller’s primary power supply is applied to terminals 9 & 11 of TB2. This may be from 10 – 30 VDC.
Aux. Relay piggy back Board shown in dotted lines RS-485 terminating resistors (remove for short wire paths & when the SafeGuard Controller is not end of path) TB2 terminals 10 & 12 provide Fused 24VDC power to the SafeGuard Controller option boards requiring such power Figure 3.1...
Page 26
• Mastr PR 0200 ms • ECHO ACK OFF Proper communication between the two devices will be confirmed by the TX1 and RX1 LEDs. Note: When configuring other Net Safety products refer to specific user manual. SafeGuard Controller User Manual MAN-0115 Rev 0...
For a 2 wire transmitter (detector), the power (+) wire is connected to the EXC terminal on the SafeGuard Analog Input Board, and the 4-20mA signal wire is connected to HI terminal on the SafeGuard Analog Input Board. See Figure 3.3 SafeGuard Controller User Manual MAN-0115 Rev 0...
JP4 as shown. This creates a wire OR function with selected channels, causing any alarm included within the zone to actuate ALL zone relays. Failsafe operation of SG10-0195 discrete relays may be programmed in the system menu as SafeGuard Controller User Manual MAN-0115 Rev 0...
Page 29
Some SafeGuard Controller applications with relays for all 48 alarms may require up to 6 boards. TB2 allows a heavier 5VDC power cable to be connected from terminals on the back of the SafeGuard Controller front panel assembly, bypassing the I C cable.
24VDC power be connected to TB2 terminals 1 & 2 as shown in Figure 3.5. Suitable power is available from the SafeGuard Controller’s Main I/O board’s TB2 terminal 10 & 12 (see Figure 3.1). The current loop (Milliamp output) is completed between High and Low Terminals.
24VDC power for the monitors or transmitters providing inputs to the SafeGuard Controller. A 150 watt AC / DC power supply may be included for these applications (115VAC or 230 VAC selected via slide switch). When ordered from the factory, it is pre-wired to provide 24VDC primary power for the SafeGuard Controller as well as any transmitters or monitors that may be connected by the end user.
However, the Diagnostics Mode can prove invaluable when testing I/O since relays and analog outputs may be stimulated without driving inputs to precise levels. Figure 4.1 SafeGuard Controller User Manual MAN-0115 Rev 0...
Page 33
* Note: The Printer Option is not used at this time.* Figure 4.2 SafeGuard Controller User Manual MAN-0115 Rev 0...
SECTION 5 5.0 MODBUS RS-485 PORTS The SafeGuard Controller is equipped with Master (COMM 1), and Slave (COMM 2), modbus RTU ports. Port configurations are described in sections 2.2 and 2.3 of this manual. Section 5.0 defines register locations of data available via the SafeGuard Controller’s slave port.
Page 35
12 bit integer for Channel Reading value = 800 counts = zero value, 4000 counts = 100% value. Type Channel First Last Read FC Write FC Notes Channel 1-16 31001 31016 12bit integer Reading SafeGuard Controller User Manual MAN-0115 Rev 0...
Page 36
Type Channel First Last Read FC Write FC Notes Sensor Life 31065 Signed 16bit integer Sensor Life 31066 Signed 16bit integer Sensor Life 31067 Signed 16bit integer Sensor Life 31068 Signed 16bit integer SafeGuard Controller User Manual MAN-0115 Rev 0...
Page 37
3 real w/o decimal point Alarm 3 DP 1-16 41145-60 alarm 3 real divisor Fault Real 1-16 41161-76 alarm 3 real w/o decimal point Fault DP 1-16 41177-92 alarm 3 real divisor SafeGuard Controller User Manual MAN-0115 Rev 0...
Page 38
0 = data ready; 1 = update in progress Trend database registers Type Channel First Last Read FC Write FC Notes 24 hr Trend 1-16 33017 36857 Transfers 24 hour trend for MAX, MIN or AVG. SafeGuard Controller User Manual MAN-0115 Rev 0...
SIDE VIEW 5.22 FRONT VIEW Note: Panel cut-out = 5.25 X 9.20 RACK / PANEL MOUNT (19” RACK SPREADER PLATES & PANEL MOUNT BEZAL NOT SHOWN) Rack Panel Mount Part # SG10-0208 Figure 6.1 SafeGuard Controller User Manual MAN-0115 Rev 0...
Bottom or lower side areas are recommended. Care must be taken to avoid drilling into circuit boards mounted inside the enclosure. Properly ground the enclosure and follow national and local electrical codes. Figure 6.2 SafeGuard Controller User Manual MAN-0115 Rev 0...
• SafeGuard N4 Wall Mount supports 3 option positions as standard and 4 more with the 10-0180 expansion plate. Figure 6.4 provides Main I/O and option PCB dimensions. Figure 6.6 Figure 6.4 SafeGuard Controller User Manual MAN-0115 Rev 0...
SECTION 7 – HOW TO RETURN EQUIPMENT A Material Return Authorization number is required in order to return equipment. Please contact Net Safety Monitoring at (403) 219-0688, before returning equipment or consult our Service Department to possibly avoid returning equipment.
• Ensure ALL personnel are educated and trained in ESD Control Procedures In general, exercise accepted and proven precautions normally observed when handling electrostatic sensitive devices. A warning label is placed on the packaging, identifying product using electrostatic sensitive semiconductor devices. SafeGuard Controller User Manual MAN-0115 Rev 0...
Page 45
Net Safety Monitoring Inc. 2721 Hopewell Place NE, Calgary, AB Canada T1Y 7J7 1‐866‐FIREGAS (347‐3427) | ph. (403) 219‐0688 | fx. (403) 219‐0694 http://www.net‐safety.com | Email: nsmsales@net‐safety.com PRODUCT SERVICES CONTACT INFORMATION Telephone [ 8am ‐ 5pm MDT ]: (403) 769‐6074 | (403) 717‐8219 Fax: (403) 219‐0694 Email: productservices@net‐safety.com http://www.net‐safety.com/service/product_services.html SafeGuard Controller User Manual MAN-0115 Rev 0...