Low-Voltage Control Wire Sizing; Electrical Data; Table 15 Recommended Minimum Wire Size; Table 16 Electrical Data-Standard Sound And Ambient Models (95°F/35°C) 60Hz - Liebert Prop Fan Condensing Unit User Manual

Prop fan condensing unit 50 & 60hz
Table of Contents

Advertisement

2.6.2

Low-Voltage Control Wire Sizing

Low-voltage wiring should be sized to allow a 1 volt maximum drop due to line resistance between the
evaporator and condensing unit. Use NEC Class 1 or 2 wiring according to wire routing conditions
chosen, local codes and application limits in Tables 14 and 15.
Table 15
Recommended minimum wire size
Max. Distance*
ft. (m)
50 (15)
100 (30)
150 (45)
*
One-way control wire run between outdoor condensing unit and evaporator.
2.7

Electrical Data

Table 16
Electrical data—Standard sound and ambient models (95°F/35°C) 60Hz
Nominal
Capacity
Model #
Tons
14
1
20
1.5
27
2
37
3
42
3.5
67
5
96
8
*
FLA = Full Load Amps
WSA = Wire Size Amps (minimum supply circuit current capacity)
OPD = Overcurrent Protection Device (fuse or circuit breaker)
Min. Wire Gauge
2
AWG (mm
)
20 (0.75)
18 (1.0)
16 (1.5)
* Electrical
Characteristic
208/230-1
FLA
WSA
11.0
OPD
FLA
12.1
WSA
14.8
OPD
FLA
13.4
WSA
16.4
OPD
FLA
18.5
WSA
22.8
OPD
FLA
WSA
OPD
FLA
WSA
OPD
FLA
WSA
OPD
Input Voltage- Phase
208/230-3
460-3
9.1
15
25
25
13.4
7.1
16.4
8.7
35
25
15
15.0
7.1
18.4
8.7
30
15
24.1
11.7
29.3
14.2
45
20
36.2
18.1
41.4
20.6
60
30
22
Installation
575-3
5.8
7.0
15
6.0
7.2
15
9.1
11.1
15
13.4
15.3
20

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents