Download Print this page

GE Unitized Spacemaker WSM2420DCC Dimension Manual page 2

General electric washer/dryer specification sheet

Advertisement

GE Appliances
®
WSM2420/80D – GE
A
A
4
Number
B
of
90°
Domestic
2-1/2
turns
dryer models
DSKS433EB
0
DSKS333EC
1
DSKP333EC
2
WSM2780H
3
0
1
2
WSM2700H
3
0
WSM2420D*
1
WSM2480D*
2
*Foil ducting not allowed
Specification Revised 5/09
360327
24" Unitized Spacemaker
For complete information, see installation instructions packed with your dryer.
Ducting Materials:
Best performance
This dryer MUST be vented with 4" diameter all rigid metal exhaust duct.
Exhaust Length Calculation:
Maximum length of 4"
1. Determine the number of 90° turns needed for your installation. If you exhaust to the side or bottom of dryer, add one turn.
dia. rigid metal duct
2. The maximum length of 4" rigid (aluminum or galvanized) duct which can be tolerated is shown in the table.
Exhaust hood type
A turn of 45° or less may be ignored. Two 45° turns within the duct length should be treated as a 90° elbow. A turn over 45° should be treated
as a 90° elbow.
Dryers must be exhausted to the outside.
A
B
Caution: For personal safety do not terminate exhaust into a chimney, under any enclosed house floor (crawl space), or into an attic, since the
4"
2-1/2"
accumulated lint could create a fire hazard or moisture could cause damage. Never terminate the exhaust into a common duct or plenum with
opening
opening
a kitchen exhaust, since the combination of lint and grease could create a fire hazard.
46 ft.
37 ft.
Exhaust ducts should be terminated in a dampered wall cap to prevent back drafts, bird nesting, etc. The wall cap must also be located at
least 12" above the ground or any other obstruction with the opening pointed down.
38 ft.
30 ft.
Special Installation Requirements
31 ft.
22 ft.
24 ft.
15 ft.
Alcove or Closet Installation:
• If your dryer is approved for installation in an alcove or closet, it will be stated on a label on the dryer back.
56 ft.
42 ft.
• The dryer MUST be exhausted to the outside.
46 ft.
36 ft.
• Minimum clearances between dryer cabinet and adjacent walls or other surfaces are:
34 ft.
28 ft.
32 ft.
18 ft.
• Minimum vertical space from floor to overhead cabinets, ceilings, etc. is 52" .
43 ft.
36 ft.
• Closet doors must be louvered or otherwise ventilated and must contain a minimum of 60 sq. in. of open area equally distributed.
33 ft.
26 ft.
If this closet contains both a washer and a dryer, doors must contain a minimum of 120 sq. in. of open area equally distributed.
23 ft.
16 ft.
• No other fuel-burning appliance shall be installed in the same closet with a gas dryer.
Bathroom or Bedroom Installation:
• The dryer MUST be exhausted to the outdoors.
• The installation must conform with the local codes, or in the absence of local codes, with the National Electric Code and National Fuel Gas
Code, ANSI Z223 for gas dryers.
Minimum Clearances other than Alcove or Closet Installation:
• Minimum clearances to combustible surfaces
®
Washer/Dryer
0" either side
3" front and rear
0" both sides
3" rear
For answers to your Monogram,
®
GE
appliance questions, visit our website at
Listed by
Underwriters
GEAppliances.com or call
Laboratories
GE Answer Center
®
GE Profile
or
®
service, 800.626.2000.

Advertisement

loading
Need help?

Need help?

Do you have a question about the Unitized Spacemaker WSM2420DCC and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

This manual is also suitable for:

Unitized spacemaker wsm2480dwwUnitized spacemaker wsm2420dwwUnitized spacemaker wsm2420dUnitized spacemaker wsm2480d