Chimney System - Lennox ELITE ME43 Installation Instructions Manual

Elite series 43" wood burning fireplaces
Table of Contents

Advertisement

Insulate Joists
Same As Ceiling
Draft Stops
Firestop
CTDT
Termination
Note: Non-
Combustible
Chase
Flashing
Must Be
Used To
Cover
Chase
Opening
8'
Level
Insulation
(Thermal Barrier)
Figure 11

CHIMNEY SYSTEM

These fireplaces are designed and code listed
for use with Security Chimneys FTF8 chimney
System only. Always use Security Chimneys
FTF8 chimney components with these fire-
places. Do not modify or alter these compo-
nents as this may cause a potential serious
hazard and void the Warranty.
*Construction Materials:
• framing materials
• particle board
• millboard
• plywood
Note: 2" clearance to combustibles around
chimney components required.
WARNING: IF INSULATION IS USED, THE
FIREPLACE MUST NOT BE PLACED DI-
RECTLY AGAINST IT. INSULATION OR
VAPOR BARRIERS, IF USED, MUST FIRST
BE COVERED WITH GYPSUM BOARD,
Optional
Insulation
PLYWOOD, PARTICLE BOARD OR OTHER
In Outside
Walls Of
MATERIAL TO ASSURE INSULATION AND
Chase
VAPOR BARRIERS REMAIN IN PLACE.
Solid
WARNING: DO NOT PACK OR FILL RE-
Continuous
Surface
QUIRED AIR SPACES WITH INSULATION
OR OTHER MATERIAL. NO MATERIAL IS
Outside
ALLOWED IN THESE AREAS.
Base
Note: Do not insulate the chase cavity with
blown or fill type insulation materials.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Note: Local codes may not require firestopping
at the ceiling levels for outside chase installa-
tions. However, it is recommended for safety
and the reduction of heat loss.
Chimney Height
The total height of your completed fireplace
system from the surface the fireplace rests on
to the chimney top must not exceed 60' and
must also meet minimum height requirements.
• paneling
Refer to the minimum system height chart.
• flooring
• dry wall
• etc.
Vertical Installation
One Offsets
Two Offsets
Chase Enclosure
A chase is a vertical box-like structure con-
structed to surround the fireplace and chimney.
Refer to Figure 11 for a typical chase configu-
ration. As with all chimney installations, avoid
overhead obstructions such as trees, power
lines, etc. A chase should be constructed and
insulated just like any outside wall. In a cold
climate, we recommend the base of the chase
should also be insulated between the solid
continuous floor beneath the fireplace and the
chase bottom. Chase insulation in a cold cli-
mate installation is not required for safety.
Minimum System Height
Security's FTF8 Pipe
15' 0"
15' 0"
25' 0"
9