FireLake 155 Owner's Manual

Multi-oil furnaces single pass/3-pass units

Advertisement

Owner's
Manual.
Multi-Oil
Furnaces
MODELS
155, 200, 245, 315 ; 235, 350, & 500
(Single pass ; 3-Pass Units)
All Installations Must Be In Accordance With State and Local Codes and it is the responsibility
of the installer to assure all codes are met
For service, call your dealer or installer at
Date Installed:
WARRANTY NOTICE
Use of equipment on any equipment not manufactured or designed for
use VOIDS the warranty - property or personal damage could occur.
Page 1 of 1

Advertisement

Table of Contents
loading

Summary of Contents for FireLake 155

  • Page 1 Multi-Oil Furnaces MODELS 155, 200, 245, 315 ; 235, 350, & 500 (Single pass ; 3-Pass Units) All Installations Must Be In Accordance With State and Local Codes and it is the responsibility of the installer to assure all codes are met...
  • Page 2: Table Of Contents

    ASSEMBLY OF OIL AND AIR SOLENOID #57190 ....................40 ASSEMBLY OF OIL REGULATOR #57129 ......................41 END OF HEATING SEASON/SUMMER STORAGE ....................43 TROUBLE – SHOOTING GENERAL ........................44 PARTS REPLACEMENT IDENTIFICATION ......................65 HEATER PARTS LIST..............................47 FIRELAKE’S WARRANTY............................71 Page 2 of 2...
  • Page 3: Specifications

    SPECIFICATIONS Model 'A' Oil Pump Model 'J' Oil Pump 1/4 " FNPT Inlet Port 1/4 " FNPT 1/8 FNPT Outlet Port 1/8 " FNPT 40-60 PSI Pressure Range 20-40 PSI 6 GPH Max. Flow 18 GPH 3450 RPM Max Allowable Speed 3450 CW Shaft End Rotation...
  • Page 4 INTRODUCTION Purchase of a multi-oil furnace is a wise investment. To maximize the return on this investment you must read and save this manual. It contains installation instructions, diagnostic procedures, burner cleaning, maintenance procedures and parts ordering information. Follow the installation instructions carefully.
  • Page 5: Packing List

    PACKING LIST Components of a Model 155, 200, 245, 315 Heater: Crated Heat Exchanger with Cabinet (remove clean out tool and parts from inside the chamber) Burner (factory test fired burner in shaped foam packaging, save box should shipping be needed) Blower Assembly (Save box.)
  • Page 6 Components of a Model 235, 350, 500 Heater: Heat Exchanger with Cabinet (remove fan, accessories, & target from inside the chamber) Burner (factory test fired burner in shaped foam packaging, save box should shipping be needed) Accessory Carton (Cleanable Oil Filter, Fan Motor, 1/2" Cutoff valve, 3/4" Suction Screen, 3/4" Check Valve, Wall Thermostat, 1/2”...
  • Page 7 MODEL 155, 200, 245, 315 HEATER COMPONENTS IDENTIFICATION STACK OUTLET BLOWER LOUVER PANEL (STACK CAP OPPOSITE SIDE) (BLANK PANEL OPPOSITE SIDE) BAROMETRIC DAMPER STACK BURNER DOOR SIDE PANEL BASE DOOR GASKET VIEW PORT BURNER (2) Bolt on brackets each end for attaching to framework or rods. Can be put on lower edge too.
  • Page 8 MODEL 235, 350, 500 HEATER COMPONENTS IDENTIFICATION LOUVERS (HOT AIR OUTLET) (LOUVERS ARE NOT USED WITH DUCTED MODELS) FAN CONTROL (OFTEN CALLED FAN LIMIT SWITCH) ELECTRICAL AND FAN RELAY JUNCTION BOXES VIEW PORT HINGED BURNER MOUNT CLEANING ACCESS PANEL FAN OPENING STACK COLLAR EXCHANGER CLEANING ACCESS PANEL Page 8 of 8...
  • Page 9 MODEL 235, 350, 500 AIR MOVER ASSEMBLY INSTRUCTIONS PROPELLER FAN ASSEMBLY Remove fan motor from carton, attach it to the wire fan guard using motor studs and nuts/washers. Place fan blade on shaft, hub away from motor. Allow 1.5” clearance from wire guard to blades. Fan will flex toward motor when running.
  • Page 10 MODEL K5 (w/Air Pump) BURNER COMPONENTS IDENTIFICATION (Actual parts may look different as Firelake often updates components to latest technologies) AIR FILTER AIR PRESSURE SWITCH OIL PRESSURE GAUGE&REGULATOR OIL FEED PIPE IGNITER SAFETY AIR PUMP OUTLET AIR PRESSURE ADJUSTING VALVE...
  • Page 11 MODEL B5 BURNER COMPONENTS IDENTIFICATION (Actual parts may look different as Firelake often updates components to latest technologies) IGNITION CONTROL (PRIMARY CONTROL) FLAME RETENTION HEAD OIL REGULATOR W/OIL CONNECTION COMBUSTION AIR INLET BANDS IGNITOR / TRANSFORMER BURNER MOUNT FLANGE RESET BUTTON...
  • Page 12: Field Assembly Instructions - Blower

    FIELD ASSEMBLY INSTRUCTIONS – MODEL 155/200/245/315 BLOWER Air Deflector Flat Side of Blower 1. Position the Air Deflector, already in the cabinet, so that the upper lip sticks out of the cabinet near the burner end. The lower ends of the Air Deflector are curved to direct the path of the air from the blower to the chimney end.
  • Page 13: Field Assembly Instructions - Burner

    FIELD ASSEMBLY INSTRUCTIONS - BURNER Upper fins are open to allow light to cad cell 7/16” center of nozzle to electrode 1/8” to 3/16” closest gap PRIOR TO INSTALLING BURNER, CHECK FOR SHIPPING DAMAGE TO FLAME RETENTION HEAD AND IGNITION ELECTRODE ALIGNMENT 2) If components are not as shown you can make adjustments to the electrodes by removing the hole plug on top of burner tube near mount flange.
  • Page 14: Heater Installation Procedure

    HEATER INSTALLATION PROCEDURE 1) Select a location for your heater observing minimum clearance to combustibles. Consider that maintenance and cleaning will be required. Allow adequate work space around burner and stack. Mount heater as low as code allows, easing service and keeping your heat at floor level.
  • Page 15: Installation Illustration -Vertical Chimney

    INSTALLATION ILLUSTRATION, ALL MODELS –VERTICAL CHIMNEY CAUTION with ALL HEATERS & CHIMNEYS Allow for adequate make-up air to enter the room where the burner operates. Allowing for a opening of 140 square inches per gallon of fuel consumed is normal. Starving the burner of air is more likely in smaller, and well insulated weather tight rooms.
  • Page 16: Alternate Stack Installation With Inducer

    ALTERNATE HORIZONTAL STACK INSTALLATION ALL MODELS USING INDUCER Confirm local building codes will allow inducers & side wall vent • Locate inducer as close to where chimney exits building as practical • • Never allow rain or condensation to flow back into heater •...
  • Page 17: Compressed Air Supply

    COMPRESSED AIR (applies to Model B5 burner only, the K5 burner has integral air pump) 1. A minimum 2 CFM at 40 psi is needed into the burner. Use a hydraulic quick disconnect or put ample flex in the line to swing burner open when servicing. A dedicated air compressor at the heater in lieu of using the shop’s air system is acceptable.
  • Page 18: Finishing The Plumbing

    FINISHING THE PLUMBING……. J Pump A Pump .1/8” Outlet Air Bleeder .1/4” Inlets Air Bleeder .1/8” Outlet .1/4” Intlet Pressure Adj. Pressure Adj. [ If Using a CDVF Pump follow instructions in CDVF Manual ] Consult your dealer for the best plumbing arrangement for your heater. There are many ways the plumbing can be done.
  • Page 19 Suction Line: Field provides piping from Check Valve to Filter. Note Check Valve has flow direction arrow. Secure piping to keep the Strainer 6”+ off the bottom of the tank. Plan ahead for routine service of components. Use minimal number of fitting to reduce chances of suction leaks.
  • Page 20: Electrical Connections

    ELECTRICAL CONNECTIONS MODELS 155, 200, 245, 235, 315, 350 All electrical wiring must meet National Electrical Code, N.F.P.A. #70 for furnaces installed in U.S., and C.S.A. Standard C22.1, Canadian Electrical Code, Park 1, for Canada. Install a panel mounted breaker for single phase 115V max 30 AMP grounded service.
  • Page 21 APPLIES TO ALL HEATER MODELS EXCEPT MODEL 500 Page 21 of 21...
  • Page 22 ELECTRICAL CONNECTIONS MODELS 500 Main blower motor(s) are 220 vac. This 220 vac motor power is kept separate from the 120 vac burner and Fan Control by the Power Relay coil. The Power Relay coil is 120 vac and is activated by the RED Fan Control wire.
  • Page 23 MODEL 500 HEATER ONLY, 220 VAC FEED Page 23 of 23...
  • Page 24 BURNERS Operating sequences and wiring diagrams follow for each model burner. Burners are factory wired and just need to be field connected to the flexible cord on the heater box. Align quick connect ends properly, slide together, then twist the nut tight. You need to know which burner you have.
  • Page 25 The red light will cycle on/off to automatically to preheat oil in block. Observe flame. A proper flame in Model 155, 200, 245, 315 will extend 1/4 to 1/3 the way down chamber approximately under where the blower is mounted. Three pass heater designs Model 235, 350, 500 will have flame approaching the target wall.
  • Page 26 10. When ignition occurs and combustion is sustained, the heat exchanger temperatures will rise. When 120° F is achieved, the fan limit switch closes, thus starting the blower to push heated air into the room. 11. When the room thermostat is satisfied, the power to the ignition system will be interrupted thus causing the burner to shut down.
  • Page 27 K5 Burner w/ Air Pump, 1 of 2 Burner Drawing Page 27 of 27...
  • Page 28 K5 Burner w/ Air Pump, 2 of 2 Burner Drawing Page 28 of 28...
  • Page 29 B5 Burner Drawing Page 29 of 29...
  • Page 30 B5 Burner Drawing Page 30 of 30...
  • Page 31 START UP AND OPERATING MODEL B5 TWO STAGE BURNER 1. Place the 3-position toggle switch on the Burner to “OFF”. Energize the heater circuit with electricity. The amber and red lights on the slide gun will come on. Flip the 3- position toggle switch on the Burner to “PRIME”.
  • Page 32 Open the bands only enough for a clean flame. Excessive air will cause irregular ignition or blow out flame. 11. Observe flame. A proper flame in Model 155, 200, 245, 315 will extend 1/4 to 1/3 the way down chamber approximately under where the blower is mounted.
  • Page 33: Initial Start Up And Operating Sequence

    120 VOLT MODEL B5 TWO STAGE (w/AIR DELAY) BURNER WIRING Page 33 of 33...
  • Page 34 HAS EXTRA AIR SOLENOID AND TIMERS 120 VOLT MODEL B5 TWO STAGE (w/AIR DELAY) BURNER WIRING Page 34 of 34...
  • Page 35: Fan Limit Switch Settings

    HAS EXTRA AIR SOLENOID AND TIMERS FAN LIMIT SWITCH SETTINGS MANUAL SELECTOR SWITCH DIAL WHEEL DIAL WHEEL 90° F, 120° F, AND 200° F SET POINTS 200° F, 120° F, AND 90° F SET POINTS Similarly operating White Rogers and Honeywell fan limit controls respectively shown above. The manual selector switch should be at AUTOMATIC for heating applications.
  • Page 36: Fine Tuning The Burner

    If resetting of tabs is needed, hold dial wheel still or force from rotating will damage coil. FINE TUNING THE BURNER OBSERVE THE FLAME DAILY. ALLOWING HEATER TO OVER FIRE WILL DESTROY THE HEAT EXCHANGER AND VOID THE WARRANTY. UNDERFIRING MAY LEAD TO CONDENSATION AND RUST THE CHIMNEY OR HEATER.
  • Page 37: Primary Control Function - Safety Lockout

    PRIMARY CONTROL FUNCTION - SAFETY LOCKOUT CAUTION: DO NOT PUSH THE RESET BUTTON IF THE BURNER FLAME FAILS AND THE FURNACE CHAMBER IS HOT! FORCING A REFIRE TOO SOON MAY PUT FUEL INTO THE HOT COMBUSTION CHAMBER AND CAUSE AN EXPLOSION HAZARD.
  • Page 38: Routine Heater And Burner Maintenance

    ROUTINE HEATER AND BURNER MAINTENANCE Weekly Maintenance A flame inspection mirror is useful for a routine check of the nozzle, ignition, and retention head while the unit is operating. 1. Observe flame--adjust if needed. 2. Check all filters and water traps in the oil and air supply lines. Clean if needed. 3.
  • Page 39: Assembly Of Nozzle

    6. Inspect o-ring; replace if worn, torn or deformed. ASSEMBLY OF NOZZLE O-RING 57186 FERRULE DISTRIBUTOR NOZZLE SIZE FOR USE WITH 57103 MODEL 155 57105 MODEL 200, 235, 245, & 315 57106 MODEL 350 57108 9-11 MODEL 500 Page 39 of 39...
  • Page 40: Assembly Of Oil And Air Solenoid #57190

    For a more thorough service the following burner components can be cleaned as a preventative yearly maintenance. BLOCK 57181 O-RING 57184 ORING 57182 PLATE 57177 ADAPTER 57179 SCREW (4) 57181 ASSEMBLY OF OIL AND AIR SOLENOID #57190 BASE * O-RING 57194 (ZINC PLUNGER W/ SPRING ASM) 57192 (NICKEL PLUNGER W/ SPRING ASM) 57139 STEM W/ WRENCH FLATS...
  • Page 41: Assembly Of Oil Regulator #57129

    ASSEMBLY OF SPECIAL MODEL 500 AIR SOLENOID #57185 BASE * O-RING 57194 (ZINC PLUNGER W/ SPRING ASM) 57192 (NICKEL PLUNGER W/ SPRING ASM) 57139 ORIFICE HOLES NOTE TWO IN BASE STEM W/ WRENCH FLATS SNAP RING COIL * Pay attention to detail, the solenoid base has a specific inlet and outlet direction. ASSEMBLY OF OIL REGULATOR #57129 BASE VALVE SPRING...
  • Page 42 For a more thorough service the aluminum preheat block can be cleaned. The need to increase oil pressures to maintain a good flame is a indicator block passages may be restricted. How quickly a block becomes restricted varies with hours of use and oil quality.
  • Page 43: End Of Heating Season/Summer Storage

    END OF HEATING SEASON/SUMMER STORAGE Consult your Dealer, they can give advice on proven methods. 1. Turn off power to furnace and set room thermostat to "off". 2. Clean furnace and chimney thoroughly. See previous sections for details. 3. Spray interior of combustion chamber with light oil to protect against corrosion. 4.
  • Page 44: Trouble - Shooting General

    For your safety switch off power supply before servicing. Only qualified persons should service equipment. TROUBLE – SHOOTING GENERAL Burner Fails To Ignite A flame requires three components: 1. fuel 2. spark 3. air . Success will come from determining which are not present and how to fix them. 1.
  • Page 45 2. Fuel pump not operating, coupler loose, bypass in pump stuck open. 3. Water, paint, or antifreeze in oil. 4. Failure of pre heater(s) in slide gun assembly. Slide gun underside should feel warm. 5. Electrodes improperly adjusted, broken, shorting, or ash covered. 6.
  • Page 46 Trouble Shooting – Fan Control NOTE JUMPERS STAY IN PLACE BLACK, BLUE, RED WIRE RED, BLACK BLUE WIRE Wires should be in proper location, secure, and probe/dial free to turn. Page 46 of 46...
  • Page 47: Parts Replacement Identification

    CAB: L or R Side 11430 CAB: Stack End, Mdl 155 100501 CAB: Stack Outlet Cover Donut 11437 CAB: Blank Filler Panel for 155 102309 CAB: Louvers(4)+ Panel Kit for 155 11242 CAB: Base for 155 102358 Louver w/bolts for 155 / Each...
  • Page 48 MOTOR: BLower MOTOR w/cap 11101 Blower Wheel & Housing for 155 &200 101140 Blower Guard for All , /Each 11103 Left Blower Housing Leg for 155 & 200 11104 Right Blower Housing Leg for 155 & 200 11107 Rubber Bushing for Leg/Each 56426...
  • Page 49 BLUE CABINET MODEL 200 Part Number Description 11440 CAB: Mdl 200 Top 11439 CAB: Mdl 200 L or R Side 11430 CAB: Stack End, Mdl 200 100501 CAB: Stack Outlet Cover Donut 11437 CAB: Blank Filler Panel for 200 12309 CAB: Louver Panel Kit for 200 11442 CAB: Base for 200...
  • Page 50 Junction Box (6"x6") 57266 STRIP: TERMINAL 8 POLE 30 AMP 57407 MOTOR: Blower Motor asm w/cap 11101 Blwer Wheel & Housing for 155 & 200 101140 Blower Guard for All /Each 11103 Blower Housing Leg-LEFT for 155 & 200 11104 Blower Housing Leg-RIGHT for 155 &...
  • Page 51 BLUE CABINET MODEL 245 Part Number Description 11740 CAB: Mdl 245 Top 11739 CAB: Mdl 245 L or R Side 11930 CAB: Stack End, Mdl 245 102353 CAB: Stack Opening Cover 11937 CAB: Blank Filler Panel for 245 100837 CAB: Louver Panel Kit for 245 11742 CAB: Base for 245 56736...
  • Page 52 56419 SWITCH: FAN 5 IN UOF 56955 Junction Box (6"x6") 57266 STRIP: TERMINAL 8 POLE 30 AMP 57406 MOTOR: Blower motor w/cap 11102 Blower Wheel & Housing for 245 101140 Blower Guard for All / Each 11105 Blower Housing Leg-LEFT for 245 11106 Blower Housing Leg-RIGHT for 245 11107...
  • Page 53 BLUE CABINET MODEL 315 Part Number Description 11940 CAB: Mdl 315 Top 11939 CAB: Mdl 315 L or R Side 11930 CAB: Stack End, Mdl 315 102353 CAB: Stack Outlet Cover Donut 11937 CAB: Blank Filler Panel for 315 100837 CAB: Louver Panel Kit for 315 11942 CAB: Base for 315...
  • Page 54 56419 SWITCH: FAN 5 IN UOF 56955 Junction Box (6"x6") 57266 STRIP: TERMINAL 8 POLE 30 AMP 57406 MOTOR: Blower motor w/cap 11102 Blower Wheel & Housing for 315 101140 Blower Guard for All / Each 11105 Blower Housing Leg-LEFT for 315 11106 Blower Housing Leg-RIGHT for 315 11107...
  • Page 55 BLUE CABINET MODEL 235 Page 55 of 55...
  • Page 56: Heat Exchanger

    Cabinet, Heat Exchanger for WO-F235 3-pass (Previously Model WO-F200) Key Item # Item Description Cabinet and Fan 56451 CAB: TOP F/235 Cabinet, Top 56452 CAB: BRNR End F/235 Cabinet, Burner End 56443 CAB: Clean-out Door 175/235 Cabinet, Clean out Door 56454 CAB: Door w handle F/175/235 Cabinet, Door with Handle (exhaust side)
  • Page 57 BLUE CABINET MODEL 350 Part Number Description 56461 CAB: TOP 8911 OPENING COVER FOR SUSPENSION LUGS 56462 CAB: BURNER SIDE 11170 CAB: BASE SKIN 8887 CAB: DOOR PANEL 6882 CAB: FAN SIDE 6846 LOUVER: REQ. 5 PER HEATER 6883 CAB: LOUVER SIDE UPPER PANEL 6884 CAB: LOUVER SIDE LOWER PANEL CAB: VERT.
  • Page 58 6775 CAB: STACK SIDE W/ 8" STACK HOLE 57453 Fan Motor only, no capacitor etc 56993 Fan Mtr Asm: w/ capacitor, elect box, etc 13142700 MT: CAPACITOR 56421 Capacitor 15 ufd 56435 BLADE: FAN 350 30DEG 1/2BORE 56437 COLLAR: SHAFT WRAP GRIP 56432 GUARD: FAN 56955...
  • Page 59 BLUE CABINET MODEL 500 Part Description Number 8889 CAB: TOP F500 BURNER SIDE 8890 CAB: TOP F500 STACK SIDE 11175 CAB: BASE SKIN 8886 CAB: BURNER SIDE 8887 CAB: DOOR PANEL 100054 CAB: VERT. LOUVER PANEL (BURNER SIDE) 6885 CAB: VERT. LOUVER PANEL (STACK SIDE) 8726 CAB: STACK SIDE, 10"...
  • Page 60 8891 CAB: LOUVER SIDE UPPER PANEL 8895 CAB: LOUVER SIDE LOWER PANEL 8911 CAB: DONUT COVER HANGING NUT 8962 LOUVER w/o bolts: 5 louvers/heater 56420 SWITCH: FAN 8 IN 55770 Motor only 1 Hp for fan (no capacitor etc) 58832 Electrical Box for mounting to Fan Mtr 58833 Lid for Elect Box on Fan Mtr...
  • Page 61 ACCESSORIES FOR BLUE HEATERS Part Description Number 56400 SCREEN: SUCTION 3/4MPT, 2.6"OD, 3.6"LG SCREEN ALT:SUCT 56401 3.4"OD,8"LG,100MESH,1.5FPT 56405 VALVE: CHECK, BRASS 3/4 FPTx3/4FPT FILTER SS CLEANABLE 100171 (HEAD,BODY,ELEMENT) 56410 FILTER ASM COMPLETE: INCL 56409,56411 BASE: USE W/ 56411 SPIN ON FILTER 56409 ELEMENT 56411...
  • Page 62 PUMP PARTS ALL MODELS Part Number Description A-Pump 55842 PUMP: MDL A, LIP, PUMP ONLY 55712 MOTOR: OIL TRANS PUMP BASE MOU 55715 COUPLING: F/TRANS PUMP 56927 GASKET: FLAT, A PUMP COVER 57264 SCREEN: FILTER STRAINER A-PUMP 55892 ADAPTER: STEEL 1/4FPTX1/8MPT J-Pump 56934 PUMP: MDL J, FACE, PUMP ONLY...
  • Page 63 BURNERS Page 63 of 63...
  • Page 64 Part Description Number Slide Gun Assemblies 56899 Slide Gun Assy. For Models up to 155 56904 Slide Gun Assy. For Model 175 56905 Slide Gun Assy. Models 235 & s 200, 245, 315 56908 Slide Gun Assy. For Model 350 56914 Slide Gun Assy.
  • Page 65 BURNERS CONTINUED Page 65 of 65...
  • Page 66 Part Number Description Slide Gun Assemblies (continued) NOZZLE ADAPTOR: W/O-RING WOF 57179 O-RING: F/ DELAVAN NOZZLE 57186 O-RING: NOZZLE ADAPTOR 3/4 OD 57182 O-RING: NOZZLE GLAND, 5/16 OD 57184 SENSOR: TEMPERATURE 140 +/-8 57146 SENSOR: TEMPERATURE 160 DEG 57149 ELEMENT: HTR CART 130W 120V 57160 ELEMENT: HTR CART 300W 1/4X905 57165...
  • Page 67 BURNERS CONTINUED Page 67 of 67...
  • Page 68 Part Number Description Slide Gun Assemblies (continued) PLUG: FEMALE ISO/GRND 57173 AIR CTRL BOX: PAINTED 235 56913 AIR CTRL BOX: ASM UOF500UL 100333 BRKT: SPPT UOF AIR CTRL BOX 56932 GROMMET: RBR5/8IDX1-1/8ODX5/16 57280 AIR PRESSURE TANK: NS PAINTED 56967 NIPPLE: BRASS NPT MALE HEX 1/8 57199 STRIP: TERMINAL 8 POLE 20 AMP 57119...
  • Page 69 Ductable parts for WOH-350 Part Number Description 86744 BLWR CABINET A/W ASM ONLY 35D CAB: BLOWER SIDE (REPLACES ROUND 56746 OPNG) 54792 ADAPTER ANGLE: 350 & 500 54791 CONNECTOR: DUCT UOF-D 57400 FILTER: AIR ALUM BLWR/MTR: KIT UOF350D 3/4 HP 57450 DIRECT DRIVE (2 REQUIRED) 115V/60HZ BLWR/MTR: KIT UOF350D/220-3/4H...
  • Page 70 Ductable parts for WOH-500 Part Number Description 56762 BLWR CAB ASM ONLY: 500D RP CAB: BLOWER SIDE (REPLACES ROUND 56749 OPNG) 54792 ADAPTER ANGLE: 350 & 500 54791 CONNECTOR: DUCT UOF-D 57400 FILTER: AIR ALUM 55787 BLWR/MTR: UOF500D 1HP/220V/60H 55789 MOTOR: BLWR 1HP/220V/60HZ 57405 BLWR: 175D-235D-500D (2C975)
  • Page 71: Firelake's Warranty

    WARRANTY USED-OIL FIRED HEATER SYSTEMS (NOT BOILERS) Firelake Mfg., LLC (“FIRELAKE”) warrants each new SHENANDOAH® Used Oil-Fired product manufactured by it to be free from defects in material or workmanship for one (1) year from and after the date of initial installation by or for the original purchaser. If such a defect is found by the Manufacturer to exist within the one (1) year period, the Manufacturer will, at its option, (a) repair or replace such product free of charge, [F.O.B.] the factory of manufacture, or (b) refund to the...
  • Page 72 SHENANDOAH® products in addition to those terms expressly stated above. An officer of Firelake Mfg., LLC must authorize any exceptions to this Warranty in writing. The Manufacturer reserves the right to change models and specifications at any time without notice or obligation to improve previous models.

This manual is also suitable for:

245200325350500235 ... Show all