The unit does not operate with the remote controller.
Also, OPERATION INDICATOR lamp does not light up by pressing EMERGENCY OPERATION switch.
Check of indoor electronic control P.C. board and indoor fan motor
C
Turn OFF the power supply.
Remove indoor fan motor connector CN211 and
vane motor connector CN151 from the indoor electronic
control P.C. board and turn ON the power supply.
Does the unit operate with the remote controller?
Does OPERATION INDICATOR lamp light up by
pressing EMERGENCY OPERATION switch?
No
Turn OFF the power supply.
Check both "parts side" and "pattern
side" of the indoor electronic control P.C.
board visually.
Indoor electronic
control P.C.Board
Varistor(NR11)
Fuse(F11)
CN211
Measure the resistance between CN211 3
and 4 of the indoor fan motor connector.
Normal value is approx. 30k' to 50k'.
Yes
Measure the resistance of the horizontal vane
motor coil.
Normal value is approx. 300' to 250'.
Replace the varistor(NR11) and fuse(F11).
Are the varistor(NR11) burnt
and the fuse(F11) blown?
Be sure to check both the fuse
and the varistor in any case.
Is the fuse(F11) blown only?
w1,2
Measure the resistance between
1(+) and 3(-) of the indoor fan
motor connector (to CN211 on the
indoor electronic control P.C. board) .
w3
w3. Short circuit:
Is the resistance 1M'
The indoor fan motor is
or more?
abnormal.
Replace the fuse (F11).
Measure the cement resistance R111 on
the indoor electronic control P.C. board.
Yes
No
No
Yes
w1. The fan motor connector's 1 lead wire is red, whereas 3 is black.
w2. Connect "+" of the tester to fan motor connector's 1 lead
wire, and "-" to 3 lead wire, otherwise the resistance cannot be
measured properly.
No
Replace the fuse (F11) and the indoor fan motor.
Yes
Is the resistance
approx. 4'?
Yes
Replace the indoor electronic control P.C. board.
19
Short circuit:
Replace the indoor fan motor.
Short circuit:
Replace the horizontal vane motor and the indoor
electronic control P.C. board.
No
Replace the indoor electronic control P.C. board
and the indoor fan motor.