GENERAL DATA

Outdoor Units
Table 1a: General Data—Outdoor Units
Cooling Mode Performance
Cooling Capacity (Btu/h)
Power Input (kW)
EER (System) / EER (ODU)
3
System SEER
3
Heating Mode Performance
Heating Capacity (Btu/h) at 47°F
Heating Capacity (Btu/h) at 17°F
Power Input (kW)
COP (ODU)
3
System HSPF
3
Operating Range
Cooling (°F DB)
Heating (°F)
Compressor
Inverter Rotary Quantity
Oil / Type
Full Load Operating RPM
Unit Data
Refrigerant Type
Refrigerant Control / Location
Maximum Number Outdoor Units / System
Maximum Number Indoor Units / System
Minimum Number Indoor Units / System
Qty Refrigeration Circuits
Sound Pressure Cooling / Heating dB(A)
Net Unit Weight (lbs)
Shipping Weight (lbs)
Communication Cable (Qty # Wires / Gauge)
Fan
Type
Qty / Motor HP
Qty / Diameter (in)
Motor / Drive
Operating Range (RPM)
Maximum Air Volume (CFM)
Maximum External Static Pressure (in-wg)
Airfl ow Direction
1. The System Combination Ratio must be
between 50–130%. See page 55 for more
information.
2. All communication cables must comply with
applicable local codes.
3. Rated using non-ducted indoor units. Rated
0 ft. above sea level with 25 ft. of refrigerant
line per indoor unit and a 0 ft. level difference
14
PRODUCT DATA
|
3.0 Ton
ARUN036GS2
38,000
3.1
11.10 / 12.26
15.90
42,000
26,400
3.4
3.62
8.50
23–118
(-4)–60
PVE / FVC68D
3600
R410A
EEV / Indoor Unit
1
1
1
5
50 / 52
234
258
2
2 / 18
Propeller (BLDC)
2 / 0.166
2 / 20.75
Brushless Digitally-Controlled / Direct
80–950
3,885
0.16
Horizontal—Back to Front
between outdoor and indoor units. All capaci-
ties are net with a Combination Ratio between
95–105%. Certifi ed under the AHRI Unitary
Small Heat Pump equipment certifi cation pro-
gram and tested per AHRI Standard 210/240
conditions and in accordance with DOE test
procedures. Nominal Cooling capacity rating
obtained with air entering the indoor coil at
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
4.0 Ton
ARUN047GS2
48,000
9.50 / 11.29
53,500
32,000
23–118
(-4)–60
1
PVE / FVC68D
R410A
EEV / Indoor Unit
1
6
1
1
51 / 53
Propeller (BLDC)
2 / 0.166
2 / 20.75
Brushless Digitally-Controlled / Direct
80–950
Horizontal—Back to Front
80°F dry bulb (DB) and 67°F wet bulb (WB)
and outdoor ambient conditions of 95°F dry
bulb (DB) and 75°F wet bulb (WB). Nominal
Heating capacity rating obtained with air
entering the indoor unit at 70°F dry bulb (DB)
and 59°F wet bulb (WB) and outdoor ambient
conditions of 47°F dry bulb (DB) and 43°F
wet bulb (WB).
ARUN053GS2
4.25
15.20
4.3
3.65
9.20
1
PVE / FVC68D
3600
EEV / Indoor Unit
1
8
1
1
234
258
2 / 18
Propeller (BLDC)
Brushless Digitally-Controlled / Direct
3,885
0.16
Horizontal—Back to Front
4. Unit is capable of operating outside the
operating range temperature limitations. See
"Select the Outdoor Unit" on page 52.
5. Sound pressure levels are tested in an
anechoic chamber under ISO Standard 1996.
6. Power wiring cable is fi eld provided and must
comply with the applicable local and national
codes.
4.4 Ton
53,000
5.51
9.00 / 9.62
14.50
59,000
38,000
5.6
3.90
8.50
23–118
(-4)–60
1
3600
R410A
1
9
1
1
52 / 54
234
258
2 / 18
2 / 0.166
2 / 20.75
80–950
3,885
0.16

Hide quick links: