Alpha CD Easy-Flue Installation Instructions

Cd easy-flue

Advertisement

Quick Links

Installation Instructions

CD Easy-Flue 500 mm Part No. 6.2000500
CD Easy-Flue 1000 mm Part No. 6.2001000
1.
GENERAL
Note: These flues MUST ONLY be used with the Alpha CD Condensing boilers.
a.
The Alpha Easy-Flue is suitable for straight horizontal flues only and can be extended up to the maximum lengths
given in paragraph (f), below.
b.
The easy-Flue includes a 90° bend, (no separate 90° bend is required).
c.
Ensure the flue assembly is installed horizontally and the inner flue duct has a slight downward slope towards the boiler.
d.
The flue system must be installed in accordance with BS 5440:1:1990.
e.
The boiler must be installed in accordance with the installation instructions supplied with the CD boiler.
f.
The CD Easy-Flues are suitable for use in the flue length ranges shown in the tables below.
Note: Where the length is less than the minimum or more than the maximum, refer to section 4.
Alpha CD Easy-Flue
KIT CONTENTS
CD Easy-Flue
B (mm)
Max
Min
500 mm
520
280
1000 mm
915
675
Fig. 1
CD Easy-Flue
B + C (mm)
Max
500 mm
460
1000 mm
855
Fig. 2
Min
220
615

Advertisement

loading

Summary of Contents for Alpha Alpha CD Easy-Flue

  • Page 1: Installation Instructions

    GENERAL Note: These flues MUST ONLY be used with the Alpha CD Condensing boilers. The Alpha Easy-Flue is suitable for straight horizontal flues only and can be extended up to the maximum lengths given in paragraph (f), below. The easy-Flue includes a 90° bend, (no separate 90° bend is required).
  • Page 2: Install The Boiler

    (refer to section 3, paragraph (c) or section 4). FIT THE FLUE The following procedure applies to fitting an Alpha CD Easy-Flue to both rear or side exit flue - horizontally only. Note: If extending the Easy-Flue refer to section 4.
  • Page 3 (use a 127 mm core drill). The size of the hole provides sufficient clearance for the clamps on the flue extension to pass through the hole. Determine the overall flue length as described in section 3, paragraph (a) to determine the number of Alpha CD 750 mm flue extensions required.
  • Page 4 These instructions have been carefully prepared but we reserve the right to Nepicar House, London Road, Wrotham Heath, alter the specification at any time in the interest of product improvement. Sevenoaks, Kent TN15 7RS © Alpha Therm Limited 2003. Tel: 0870 3001964 email: info@alphatherm.co.uk website: www.alpha-boilers.com...

This manual is also suitable for:

6.20005006.2001000