Alpha CB Boiler Installation Instructions

Vertical flue terminal assembly twin pipe (80 mm) flue system

Advertisement

Installation Instructions
Vertical Flue Terminal Assembly
Twin Pipe (80 mm) Flue System

1. GENERAL

a.
The flue system must be installed in accordance with BS 5440:1:1990.
b.
The boiler must be installed in accordance with the installation instructions supplied with the boiler and the twin
pipe flue instructions supplied with the boiler conversion kit.
c.
The vertical flue terminal assembly is equivalent to 1.0 m of flue length.
d.
Refer to the vertical flue options in Fig. 1 and ensure that the flue length (H) does not exceed the equivalent of
7.0 m.
e.
Each 45° bend is equivalent to 0.5 m of length of flue and no more than four bends must be used in each flue
exhaust or air inlet duct.
Note: 90° bends must not be used with the vertical flue.
f.
Additional flue/air ducting is available in 1.0 m lengths for extending the flue up to a maximum equivalent flue
length of 7.0 m.
g.
The vertical terminal may be connected directly to the boiler via the conversion kit. However, under no
circumstances must the terminal be shortened in length.
h.
To determine the total length (A) of flue/air ducting required (refer to Fig. 1).
Measure the distance (X) from the top of the boiler side panel to the weathering slate position and subtract 640
mm for the terminal assembly, i.e. C = X - 640 mm
A = 2 x C + (50 mm for each connection in straight ducting).
Alpha CB/C/SY Boiler
(Kit Part No. 6.1000369)
KIT CONTENTS

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Alpha CB Boiler and is the answer not in the manual?

Questions and answers

Summary of Contents for Alpha Alpha CB Boiler

  • Page 1: Installation Instructions

    Installation Instructions Alpha CB/C/SY Boiler Vertical Flue Terminal Assembly Twin Pipe (80 mm) Flue System (Kit Part No. 6.1000369) KIT CONTENTS 1. GENERAL The flue system must be installed in accordance with BS 5440:1:1990. The boiler must be installed in accordance with the installation instructions supplied with the boiler and the twin pipe flue instructions supplied with the boiler conversion kit.
  • Page 2 Fit a weathering slate, suitable for a 125 mm outside diameter flue, over the hole in the roof. A suitable weathering slate (Part No. 6.1000380) is available from Alpha Therm Ltd. Fit the terminal assembly into the weathering slate and place it in position, ensuring the minimum distances given in Fig.

This manual is also suitable for:

Alpha sy boiler6.1000369Cb seriesC seriesSy series

Table of Contents