(12) -2
Electric heater operating mode setting
〈When electric heater is used in "Heat Pump lockout
mode"〉
•
Check the heater capacity. (Select heater marked with "
2
"
" in Table 8.)
•
Perform on-site setting using the remote controller.
•
Set the "heat pump lockout mode" using the outdoor unit.
(Refer to the service manual for the outdoor unit.)
〈When used as "Auxiliary electric heater"〉
•
Check the heater capacity. (Select heater marked with "
Table 8.)
•
Perform on-site setting using the remote controller.
Table 8
Electric heater kit model name
Model
HKR-
HKR-
HKR-
03
05C
12 type
1
18 type
24 type
1
30 · 36 type
1
1
1
1
42 type
48 · 54 type
1
1
Electric Heater kit setting
Mode No.
(Optional kit)
Heat Pump lock out mode
Auxiliary electric heater &
Heat Pump Lockout mode
available
* factory set
(12) -3
Electric heater ON/OFF temperature setting
•
While in heating operation, the heater control (ON/OFF) is
conducted as shown below;
ON
<Ton: F°>
•
Perform on-site setting using the remote controller.
FIRST
Mode
CODE
CODE
No.
01*
NO.
<Ton>
-7.2
10 (20)
7
<Toff>
-3.6
* factory set
10-6
SETTING FOR LOCAL SUPPLIED OPTION.
(1)
Installation of the humidifi er, economizer and air
purifi er (UV lamp)
•
Humidifi er, economizer and air purifi er (UV lamp) are
sold separately. For the method of installation, refer to
the manual provided with each optional product.
English
HKR-
HKR-
HKR-
HKR-
06
08C
10C
15C
20C
1
1
2
1
1
2
FIRST
SECOND
CODE NO.
CODE NO.
01*
03
11 (21)
3
Set temperature
OFF
<Toff: F°>
SECOND CODE NO.
02
03
04
05
06
-6.3
-5.4
-4.5
-3.6
-2.7
-2.7
-1.8
-0.9
0
0.9
WARNING
•
If the unit is installed with an electric heater, install the
optional product at a location where it is not exposed directly
" or
to the heat from the electric heater. Direct exposure to heat
can result in an equipment malfunction or fi re.
(2)
Connect the wires
•
Run the wires through the low-voltage hole.
•
Connect the wires to the terminal block (10P) of the
1
" in
product. The terminal Nos. for wire connection are
shown below. Refer to the information as needed.
Terminal Nos. are indicated on the name plate for the
terminal block.
2
Terminal No. Input/output signal
1, 2
3, 4
5, 6
7, 8
9, 10
(3)
On-site setting of air purifi er/humidifi er
Mode No. FIRST CODE NO .
14 (24)
4
FAN SPEED
UNDER
OPERATING
purifi er and
humidifi er
14 (24)
5
FAN RESI-
DUE TIME
FOR HUMIDI-
FIER
* factory set
10-7
SETTINGS FOR SEPARATELY SOLD ACCES-
SORIES
•
See the instruction manuals included with optional accesso-
ries for the necessary settings.
Outputs: indoor unit ON signal. (AC 24V)
Outputs: indoor unit cooling THERMO ON
signal. (AC 24V)
Receives input: Air purifi er operation ON
signal. (dry contact)
Receives input: Humidifi er operation ON
signal. (dry contact)
Receives input: Forced closure of Indoor Unit
Electronic Expansion Valve during cooling
operation. (dry contact)
01
02
Refer to
remote
controller
H*
setting
SPEED
30 [sec]
60* [sec]
Terminal
block (10P)
03
120 [sec]
16