(12) -2
Electric heater operating mode setting
〈When electric heater is used in "Heat Pump lockout
mode"〉
Check the heater capacity. (Select heater marked with "
2
"
" in Table 8.)
Perform on-site setting using the remote controller.
Set the "heat pump lockout mode" using the outdoor unit.
(Refer to the service manual for the outdoor unit.)
〈When used as "Auxiliary electric heater"〉
Check the heater capacity. (Select heater marked with "
Table 8.)
Perform on-site setting using the remote controller.
Table 8
Electric heater kit model name
Model
HKR-
HKR-
HKR-
03
05C
12 type
1
18 type
24 type
1
30 · 36 type
1
1
1
1
42 type
48 · 54 type
1
1
Electric Heater kit setting
Mode No.
(Optional kit)
Heat Pump lock out mode
Auxiliary electric heater &
Heat Pump Lockout mode
available
* factory set
(12) -3
Electric heater ON/OFF temperature setting
While in heating operation, the heater control (ON/OFF) is
conducted as shown below;
ON
<Ton: F°>
Perform on-site setting using the remote controller.
FIRST
Mode
CODE
CODE
No.
01*
NO.
<Ton>
-7.2
10 (20)
7
<Toff>
-3.6
* factory set
10-6
SETTING FOR LOCAL SUPPLIED OPTION.
(1)
Installation of the humidifi er, economizer and air
purifi er (UV lamp)
Humidifi er, economizer and air purifi er (UV lamp) are
sold separately. For the method of installation, refer to
the manual provided with each optional product.
English
HKR-
HKR-
HKR-
HKR-
06
08C
10C
15C
20C
1
1
2
1
1
2
FIRST
SECOND
CODE NO.
CODE NO.
01*
03
11 (21)
3
Set temperature
OFF
<Toff: F°>
SECOND CODE NO.
02
03
04
05
06
-6.3
-5.4
-4.5
-3.6
-2.7
-2.7
-1.8
-0.9
0
0.9
WARNING
If the unit is installed with an electric heater, install the
optional product at a location where it is not exposed directly
" or
to the heat from the electric heater. Direct exposure to heat
can result in an equipment malfunction or fi re.
(2)
Connect the wires
Run the wires through the low-voltage hole.
Connect the wires to the terminal block (10P) of the
1
" in
product. The terminal Nos. for wire connection are
shown below. Refer to the information as needed.
Terminal Nos. are indicated on the name plate for the
terminal block.
2
Terminal No. Input/output signal
1, 2
3, 4
5, 6
7, 8
9, 10
(3)
On-site setting of air purifi er/humidifi er
Mode No. FIRST CODE NO .
14 (24)
4
FAN SPEED
UNDER
OPERATING
purifi er and
humidifi er
14 (24)
5
FAN RESI-
DUE TIME
FOR HUMIDI-
FIER
* factory set
10-7
SETTINGS FOR SEPARATELY SOLD ACCES-
SORIES
See the instruction manuals included with optional accesso-
ries for the necessary settings.
Outputs: indoor unit ON signal. (AC 24V)
Outputs: indoor unit cooling THERMO ON
signal. (AC 24V)
Receives input: Air purifi er operation ON
signal. (dry contact)
Receives input: Humidifi er operation ON
signal. (dry contact)
Receives input: Forced closure of Indoor Unit
Electronic Expansion Valve during cooling
operation. (dry contact)
01
02
Refer to
remote
controller
H*
setting
SPEED
30 [sec]
60* [sec]
Terminal
block (10P)
03
120 [sec]
16