Compressor Operation with VFD Drive
Start
Compressor
Start VFD at
Minimum Speed
(30 Hz Typ.)
VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
Operational Flow Charts
Is Control Press.
Within Setpt
No
Deadbands?
Yes
Check/Adjust VFD
Is Control Press @
No
Setpoint?
Yes
Is Motor Speed @
No
Min?
Check/Adjust Capacity Slide
No
Increase or Decrease the
Compressor Capacity Slides to
Match Setpoints
Increase or Decrease the
Compressor Capacity Slides to
Match Setpoints
Increase or Decrease Motor Speed
@ Rate Defined by VFD PID
Parameters
Is Capslide @
100%
Yes
13