Download Print this page
CyberPower PR1000LCDRTXL2Ua User Manual
CyberPower PR1000LCDRTXL2Ua User Manual

CyberPower PR1000LCDRTXL2Ua User Manual

Smart app sinewave series

Advertisement

Quick Links

Smart App Sinewave Series
PR1000LCDRTXL2Ua/PR1500LCDRTXL2U/
PR2200LCDRTXL2U
User's Manual

IMPORTANT SAFETY WARNINGS

This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. Please read
and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install,
or operate.
CAUTION! The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection. DO NOT plug the UPS into an
outlet that is not grounded. If you need to power-drain this equipment, turn off and unplug the unit.
CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! Under no circumstances this unit should be used for medical
applications involving life support equipment and/or patient care.
CAUTION! The battery can power hazardous components inside the unit, even when the AC input power is disconnected.
CAUTION! The UPS should be near the connected equipment and easily accessible.
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area, free of conductive
contaminants. (Please see specifications for acceptable temperature and humidity range).
CAUTION! To reduce the risk of an electric shock, do not remove the cover, except to service the battery. There are no user serviceable parts
inside, except for the battery.
CAUTION! To avoid electrical shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a
computer component.
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire, do not use with or near aquariums. Condensation from
the aquarium can come in contact with metal electrical contacts and cause the machine to short out.
CAUTION! DO NOT USE WITH LASER PRINTERS! The power demands of laser printers are too large for a UPS.

INSTALLING YOUR UPS SYSTEM

UNPACKING
Inspect the UPS upon receipt. The box should contain the following.
(1) UPS Unit; (1) User's Manual for UPS; (2) Rack mount Brackets; (2) Stands; (2) Skids; (1) Telephone Cable (black); (1) Emergency Power Off
®
Cable (gray); (1) PowerPanel
Business Edition Software CD; (2) Serial Interface Cable (DB-9); (1) USB A+B type cable; (1) Warranty
Registration Card.
OVERVIEW
The PR1000LCDRTXL2Ua/PR1500LCDRTXL2U/PR2200LCDRTXL2U provides battery backup, automatic
voltage regulation (AVR), and optimal performance of computers and other network equipment by ensuring
consistent
sinewave
power.
The
PR1000LCDRTXL2Ua/PR1500LCDRTXL2U/PR2200LCDRTXL2U
features 2060 Joules of surge protection, and provides battery backup during power outages. The
PR1000LCDRTXL2Ua/PR1500LCDRTXL2U/PR2200LCDRTXL2U ensures consistent power to your
computer system and its included software will automatically save your open files and shutdown your
computer system during a utility power loss.
AUTOMATIC VOLTAGE REGULATOR(AVR)
The PR1000LCDRTXL2Ua/PR1500LCDRTXL2U/PR2200LCDRTXL2U can stabiliz the consistent utility power. The utility power may be
damaging to important data and hardware, but Automatic Voltage Regulation helps the computer not experience dangerous voltage levels.
Automatic Voltage Regulator automatically regulates low or high voltages to keep equipment working at safe AC power levels (110/120V) without
switching to battery. Your equipment can operate normally even meet the power problems, such as, shout brownouts and blackouts. The unit's
powerful sealed lead-acid batteries will provide power only if the incoming voltage drops below 80V or increases above 150V.
SYSTEM BLOCK DIAGRAM
HARDWARE INSTALLATION GUIDE
1. Battery charge loss may occur during shipping and storage. For the first time the UPS is used, it's strongly
recommended to charge batteries for at least eight hours is recommended to ensure that the batteries' maximum
charge capacity. To recharge the batteries, simply make the UPS plugs into an AC outlet.
2. When you use the included software, connect either the serial or the USB cable between the computer and the
corresponding port on the UPS. Note: If the USB port is used, the serial port will be disabled. They cannot be
®
used simultaneously. The computer with the PowerPanel
Business Edition S/W connects to the USB port or the
Serial port on the UPS. It can control the operating schedule, battery test, outlet, etc. and get information on the
UPS status. However, other computers with PowerPanel
information via a LAN connection.
3. With the UPS off and unplugged, connect your computer, monitor, and any externally powered data storage
device (Hard drive, Tape drive, etc.) into the outlets. DO NOT plug a laser printer, copier, space heater, vacuum,
paper shredder or other large electrical device into the UPS. The power demands of these devices will overload
and possibly damage the unit.
4. To protect a fax, telephone, modem line or network cable, connect the telephone or network cable from the
wall jack outlet to the jack marked "IN" of the UPS. Then, connect a telephone cable or network cable from the
jack marked "OUT" on the UPS to the modem, computer, telephone, fax machine, or network device.
5. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is
protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air
conditioner, refrigerator, copier, etc.). Avoid using extension cords.
6. Press the power switch to turn the UPS on. The Power-On indicator light will illuminate. If an overload is
detected, an audible alarm will sound and the UPS will emit one long beep. In order to reset it, turn the unit off
and unplug some equipment from outlets. Make sure your equipment carry a load current within the unit's safe
range, (refer to the technical specifications), and then turn the unit on.
7. Your UPS is equipped with an auto-charge feature. When the UPS is plugged into an AC outlet, the battery will
be automatically charging, even when the unit is switched off!
8. To always maintain an optimal battery charge, leave the UPS plugged into an AC outlet at all times.
9. Before storing the UPS for an extended period of time, turn the unit OFF. Then cover it and store it with the
batteries fully charged. Recharge the batteries every three months or so, to ensure good battery capacity and
long battery life; further, this might also prevent damage to the unit from an unlikely battery leakage.
10. The unit provides one Primary Serial Port (I), Secondary Serial Port (II), and one USB port, (paired with the
Primary Serial Port), to allow connection and communication between the unit and any attached computers. The
Primary Serial Port (I) as well as its paired USB port allow for bi-directional communication among the UPS and
®
the primary connected computer running the PowerPanel
the computer's shutdown in case of an emergency, and at the same time, the computer can monitor the UPS and
alter its various programmable parameters. On the other hand, secondary Serial Port II only allows the UPS to
initiate the connected computer's graceful auto-shutdown in case of an emergency.
11. EPO (Emergency Power Off) Port:
Use the provided gray cable to connect to a special EPO contact switch. Follow the appropriate circuit diagram
below to wire the cable to your EPO configuration. The EPO remote switch is a switch installed in an outside area,
connected to the unit via an ordinary RJ-11 phone line. In case of an emergency, it can be used to immediately
cut-off power from the UPS.
®
Dry connect is controlled by the PowerPanel
Software, please
go to
www.cyberpowersystems.com
for free download.
*NOTE: Both USB and Serial cannot be used simultaneously.
®
Business Edition S/W can only get UPS status
When you first receive the
unit, plug in the unit to fully
charge the battery.
Unplug the unit and turn Power
Off when first connecting your
computer and peripherals.
Business Edition S/W provided. The UPS can control
The primary computer
The equipment can
®
with PowerPanel
read information
Business Edition
via dry contact.
software connected to
the UPS with either a
serial cable or a USB
cable.
FRONT / REAR PANEL DESCRIPTION
1. Power Switch
Master on/off switch for equipment connected to the UPS.
2. Power On Indicator
Indicates the power is on.
3. LCD Module Display
LCD shows all the UPS information with icons and messages.
4. LCD Display Toggle Button
The button can be used to toggle between different data displays
on the LCD.
K01-0000071-01
5. Battery Backup Protected Outlets
The unit provides a total of eight outlets with battery backup and
surge protection. They ensure that connected equipment will
keep an uninterrupted operation over a period of time, during a
power failure.
Critical /Non-critical
It is possible to program the unit in a way so that the outlet block
marked as "non-Critical", (4 ports), will stop the provision of
power to connected equipment after a certain period of time,
thus making more runtime available for the equipment
connected on the outlets marked as "Critical", (2 ports). In other
words, the user can establish runtime priority for certain
connected equipment, maximizing its "availability" during a
prolonged power outage. This type of control takes place with
the use of the provided PowerPanel
6. Input Power Cord
Connect the AC Power cord to a properly wired and grounded
outlet.
7. Output Circuit Breaker
This circuit breaker serves to provide output overload and fault
protection.
8. Input Circuit Breaker
This circuit breaker serves to provide input overload and fault
protection.
9. USB port
This is a connectivity port allowing communication and control
among the UPS and the connected computer. You should install
on your computer the PowerPanel
appropriate to the operating system you are using.
Contact your dealer, or email tech@cpsww.com. Refer to replacement battery pack number RBP852 for PR1000LCDRTXL2Ua/
PR1500LCDRTXL2U/ PR2200LCDRTXL2U.
For model PR1000LCDRT2Ua, PR1500LCDRTXL2U, PR2200LCDRTXL2U can support model BP48V75ART2U for external battery pack.
Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery. Service the battery under the supervision of
personnel knowledgeable of batteries and their precautions. Servicing the battery should only be performed by trained personnel.
Replacement of batteries located in an OPERATOR ACCESS AREA.
CAUTION!
When replacing batteries, replace with the same number of the following battery: HR9-12(BB) for PR1000LCDRTXL2Ua/
PR1500LCDRTXL2U/ PR2200LCDRTXL2U,
CAUTION! Risk of Energy Hazard, 12 V, maximum 9Ampere-hour battery (HR9-12). Before replacing batteries, remove conductive jewelry
such as chains, wrist watches, and rings. High energy through conductive materials could cause severe burns.
CAUTION! Risk of battery explosion, if battery is replaced by an incorrect type. Dispose of used battery according to the instructions.
CAUTION! To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit overcurrent protection in
accordance with the National Electric Code, ANSI/NFPA 70.
CAUTION! Use only the specified CyberPower replacement battery, or battery pack. See your dealer for details.
CAUTION! The battery may present a risk of electrical shock. Do not dispose of batteries in a fire, as they may explode. Follow all local
ordinances regarding proper disposal of batteries.
CAUTION! Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes and may be toxic.
CAUTION! A battery may present a high risk of short circuit current and electrical shock.
Take the following precautions before replacing the battery:
1. Remove all watches, rings or other metal objects.
2. Only use tools with insulated handles.
3. Do not lay tools or metal parts on top of battery or any terminals.
4. Wear rubber gloves and boots.
5. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of ground. CONTACT WITH A GROUNDED
BATTERY CAN RESULT IN ELECTRICAL SHOCK! The likelihood of such shock will be reduced if such grounds are removed during installation
and maintenance (applicable to a UPS and a remote battery supply not having a grounded circuit)
BATTERY REPLACMENT PROCEDURE:
.
1.Remove the six retaining screws,
and remove the front panel.
4. Disconnect the black and red cable
The LCD displays detailed
information on the UPS status
and current power conditions
to alert you to potential power
problems before the affect
your equipment. Note! All
related UPS information is
based on that you should turn
on the UPS.
Automatic Voltage Regulation (AVR) icon: This icon will appear when the unit is automatically regulating low or high AC input line voltage
conditions, without resulting to the use of battery power.
SILENT MODE icon: This icon appearing indicates that the buzzer will not be beeping while in battery operating mode. During Silent mode, the
unit's alarm does not sound until the Battery Capacity falls to < 20%.
OVER LOAD icon: This icon will appear followed by an alarm, indicating that an overload condition has been reached. To recover from the
overload condition, start unplugging your equipment from the UPS outlets until the icon disappears and the alarm stops.
FAULT icon: When activated indicates a system fault error. Please refer to the troubleshooting table for possible causes and solutions.
BATT. CAPACITY meter: BATT. CAPACITY is shown as a bar chart; each segment indicates approximately a 20% of battery capacity.
LOAD CAPACITY: Load CAPACITY is shown as a bar chart; each segment indicates approximately a 20% of load capacity.
LOAD CAPACITY: This meter displays the approximate output load level (in 20% increments) of the UPS's battery outlets.

BASIC OPERATION

10. Protected Communication Ports RJ11/RJ45
Ports protect standard single line modem, fax, telephone line or network
cable.
11. Site Wire Fault Indicator
This LED will illuminate to warn the user that a wiring problem exists within
the AC receptacle, such as a bad ground or reversed wiring. If illuminated,
disconnect all equipment and contact an electrician to ensure outlet is
properly wired.
12. Coax/Cable/DSS Surge Protection
The Coax/Cable/DSS surge protection ports will protect any cable Modem,
CATV converter or DSS receiver.
®
Business Edition S/W.
13. Serial Port I
Serial port allows connection and communication between the UPS and the
computer.
14. Serial Port II
Serial Port II relays information to equipment that can utilize a contact
closure UPS.
15. SNMP/HTTP Network slot
Remove the cover panel to install optional SNMP that allows remote
monitoring and control of your UPS on a network.
16. EPO (Emergency Power Off) Port
Allow for an emergency UPS Power-Off from a remote location.
17. Ground Stud
Use the Ground Stud to ground the UPS.
®
Business Edition S/W
18.External Battery Pack Connector
Provides a connection for additional CyberPower external battery packs for
extended runtime.

BATTERY REPLACEMENT

2. Remove the two retaining screws of
3. Remove the two retaining screws of the cable
the cable protection cover then remove
connectors.
the cover.
5. Remove the three retaining screws.
6. Pull out the old battery pack and replace.
Reassemble the retaining screws, covers, black and
red cable, and front panel in the reverse sequence
of the above steps. Recharge the unit for 4-8 hours
to ensure maximum UPS battery runtime.
LCD STATUS DEFINITION
INPUT voltage meter: This meter measures the AC voltage from the wall outlet. The INPUT voltage readout
is used to identify the input voltage information. This can be used as a diagnostic tool to identify poor-quality
input power. Units are listed in V (Volts). When the UPS connect to any equipment, the AVR can provide a
stable 110/120V power output. In the event of a complete loss of power, severe brownout, or over voltage,
the UPS relies on its internal battery to back up to supply a consistent 110/120V output.
OUTPUT voltage meter: The Output Voltage screen measures, in real time, the AC voltage that the UPS is
providing to your connected equipment via the UPS outlets. Units are listed in V (Volts).
ESTIMATE RUN TIME: The Estimated Runtime Screen displays how many minutes of runtime can be
expected of the UPS if it were to experience a power outage. When runtime becomes shorted, the battery
capacity will decrease; (battery capacity bar indicator will be falling.) Note: The number displayed may be less
than actual runtimes for low loads.
NORMAL icon: This icon illuminates when the UPS is working under normal conditions.
BATTERY icon: When there is a severe brownout or blackout, this icon will appear followed by an alarm,
(two short beeps), indicating that the UPS is now working using its internal batteries. Once the batteries are
run out of power, (over a period of time), a constant alarm will sound. If this happens and main power has not
been restored, it is recommended that you save your files and turn off your equipment manually as soon as
possible.

Advertisement

loading

Summary of Contents for CyberPower PR1000LCDRTXL2Ua

  • Page 1: Basic Operation

    BATTERY REPLACEMENT The PR1000LCDRTXL2Ua/PR1500LCDRTXL2U/PR2200LCDRTXL2U provides battery backup, automatic voltage regulation (AVR), and optimal performance of computers and other network equipment by ensuring Contact your dealer, or email tech@cpsww.com. Refer to replacement battery pack number RBP852 for PR1000LCDRTXL2Ua/ consistent sinewave power.
  • Page 2: Technical Specifications

    If the Product is defective in material or workmanship, CyberPower will repair or replace it at CyberPower's expense, or, if CyberPower is unable to or decides not to repair or replace the Product (if defective) within a reasonable time, CyberPower will refund to you the full purchase price you Turn the UPS off and unplug at least one piece of equipment.

This manual is also suitable for:

Pr1500lcdrtxl2uPr2200lcdrtxl2u