Gas Supply Piping - RBI SPECTRUM Series Installation & Operation Manual

Spectrum finned copper gas boilers (model sb) & water heaters (model sw)
Table of Contents

Advertisement

GAS SUPPLY PIPING

WARNING: Check the boiler/water heater rating
plate to make sure that the boiler/water heater is
for the type of gas that will be used. If it isn't, do
not connect the boiler/water heater to the gas
supply. Gas supply piping must be in accordance
with the National Fuel Code, ANSI Z223.1-latest
revision or applicable provisions of the local
building codes. Canadian Installations must
comply with CAN/CGA B149.1 or .2 Installation
Code. Failure to comply with this warning can
result in extensive property damage, severe
personal injury or death!
The Spectrum boiler/water heaters come from the
factory ready to be piped to the gas supply. If for any
reason the boiler/water heater is not for the type of gas
available at the installation site, call the nearest RBI
representative to resolve the problem.
NOTE: A minimum gas supply pressure of 5 in,
127 mm W.C. natural or 12 in, 305 mm W.C. propane
and maximum gas supply pressure of 14 in,
356 mm W.C. natual or propane, must be available
at the safety shutoff valve inlet with the unit(s)
operating.
Table 10 should be used to ensure that the gas supply
piping is sized properly. If more than one appliance is
supplied by the same supply pipe, the piping must be
sized based on the maximum possible demand. Do not
neglect the pressure drop due to pipe fi ttings. Table 10
should be used in conjunction with Table 11 to ensure
that the gas supply piping has the capacity to meet the
demand.
Table 10 - Gas Pipe Capacity
Maximum pipe capacity in ft
at a pressure of 0.5 psig or less and a 0.3" W.C. pressure drop.
Nominal
10
20
30
Iron Pipe
Size, (in)
Maximum gas volume of pipe, (ft
3/4"
278
190
152
1"
520
350
285
1 1/4"
1050
730
590
1 1/2"
1600
1100
890
2"
3050
2100
1650
2 1/2"
4800
3300
2700
3"
8500
5900
4700
4"
17,500
12,000
9700
Note: Multiply the gas volume by 0.62 for propane fl ow capacity in ft
Multiply the propane fl ow capacity by 2500 Btu/ft
capacity for a given pipe size and length.
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS
3
/hr based on 0.60 specifi c gravity gas
Pipe length in feet
40
50
60
80
100
3
/hr)
130
115
105
90
245
215
195
170
500
440
400
350
760
670
610
530
1450
1270
1150
990
2300
2000
1850
1600
1400
4100
3600
3250
2800
2500
8300
7400
6800
5800
5100
3
/hr.
3
to determine the propane Btu/hr
Table 11 - Equivalent Pipe Length
Iron Pipe
Size, (in)
Notes: 1. For fl ow through branch.
Figure 10 depicts the proper way to connect the
boiler/water heater to the gas supply piping. The manual
shut-off valve MUST be installed in the supply piping. It
should be installed 5 ft, 1.5 m above the fl oor where
required by local codes. Provide a sediment trap at the
bottom of the vertical section of the gas supply pipe
upstream of the gas controls.
A ground joint union should be installed between the
boiler gas controls and the supply piping. Each of these
items are needed to ensure long life and ease of
servicing. Always use a pipe sealant that is suitable for
use with LP gas.
Figure 10 - Gas Supply Piping
150
79
64
CAUTION: Always use a wrench on the gas valve
150
120
body when making gas connections to it. Never
305
250
over-tighten the piping entering the gas valve body
460
380
or gas valve failure may result!
870
710
1130
2000
4100
Type of pipe fi tting
Nominal
90°
Elbow
Tee
1
Equivalent of pipe length (ft)
1"
2.6
5.2
1 1/4"
3.5
6.9
1 1/2"
4.0
8.0
2"
5.2
10.3
2 1/2"
6.2
12.3
3"
7.7
15.3
4"
7.7
15.3
2. For fl ow at full open.
Page 17
Gate
Gas
Valve
2
Cock
2
0.6
1.5
0.8
1.9
0.9
2.3
1.2
3.0
1.4
3.7
1.8
4.5
1.8
4.5
RIOM-47

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SbSwSb seriesSw series

Table of Contents