24
© Baxi Heating UK Ltd 2008
4.0
Maintenance
4.1
Check heat transfer fluid
The heat transfer fluid must be checked every year with regard
to its antifreeze and pH value.
-
Check antifreeze using antifreeze tester.Target value is
approximately -21 deg C (40% concentration).
4.2
Maintenance of the collector
The collector or the collector array must be checked/serviced
annually to check for any damage, leaks and contamination.
4.3
Cylinder
Refer to manufacturers documentation.