TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
NOTE: There is a 5°F deadband between Compressor and
Auxiliary Heat lockout temperatures
Operation in Heat Mode
When the outdoor temperature is:
— Below Compressor Lockout Temperature: only Auxiliary
Heat operates.
— Above Auxiliary Lockout Temperature: only the Compressor
operates.
— Between the two temperatures: both the Compressor and
Auxiliary Heat operate.
COMPRESSOR ONLY
50
BOTH COMPRESSOR AND
AUXILIARY HEAT
35
AUXILIARY ONLY
Fig. 41. Heat Pump Operation with Lockout Temperatures
Operating Sequence
The thermostat energizes specific terminal(s), depending on
the demand for heating, cooling or fan. The thermostat screen
shows the time, inside temperature, system and fan selections.
Additional indicators are shown when the heating, cooling or
fan is energized. See Tables 9 and 10 for specification
information.
Table 9. Sequence of Operation for Conventional Systems.
System
Fan
Setting
Setting Call for Action
Off
Auto
Cool
Auto
Cool
Auto
Stage 1
or Auto
Cooling
Cool
Auto
Stages 1 and 2
or Auto
Cooling
Heat
Auto
Heat
Auto
Stage 1
or Auto
Heating
Heat
Auto
Stages 1 and 2
or Auto
Heating
a
If Installer Setup System type is set to two stages of cooling.
b
G energizes only if Installer Setup 0180 is set to Electric.
c
If Installer Setup System type is set to two stages of heating.
63-2635—03
AUXILIARY
LOCKOUT
TEMPERATURE
COMPRESSOR
LOCKOUT
TEMPERATURE
M19950
Set.
Energize
Screen
Terminals
Message
Y, G
Cool On
a
Cool On
Y, Y2
, G
b
Heat On
W, G
Heat On
c
b
W, W2
, G
Table 10. Sequence of Operation for Heat Pump Systems.
System
Fan
Setting
Setting Call for Action
Off
Auto
Cool
Cool
Auto
Stage 1 Cooling
or Auto
Stages 1 and 2
Cooling
Heat
Auto
None
Heat
Auto
Stage 1 Heating
or Auto
Stages 1 and 2
Heating
Stages 1, 2 and 3
Heating
a
Configure O/B in Installer Setup. Based on last piece of
equipment called (cooling = O; heating = B).
b
If Installer Setup System Type is set to 3Heat/2Cool Heat
Pump with Auxiliary Heat.
c
If Installer Setup System Type is set to 2Heat/1Cool Heat
Pump with Auxiliary Heat.
d
This terminal does not energize if Installer Setup System type
is set to 2 Heat/2 Cool Heat Pump with no Auxiliary Heat.
Second Stage Heat and Cool Control
While maintaining setpoint, several factors affect when 2nd
stage energizes such as load conditions, environmental
conditions, P+I control, and home insulation. The second stage
energizes when the thermostat senses 1st stage is running at
90% capacity. This operation is droopless control.
Temperature Sensor Operation and Checkout
Allow outdoor or indoor temperature sensor to absorb the air
for a minimum of five minutes before taking a reading. See the
Sensor instructions for more information.
NOTE: The C7089U, C7189U, and T7770A Temperature
Sensors are calibrated at the factory and cannot
be recalibrated in the field.
C7089U Outdoor Temperature Sensor

Operation

When installed with Thermostat ISU 0340 set to 1 or 2, the
thermostat can display outside temperature.
Checkout
Allow C7089U Outdoor Sensor to absorb outdoor air for a
minimum of twenty minutes before taking a reading.
With an accurate thermometer (±1°F [0.5°C]) measure the
temperature at the sensor location, allowing time for the
thermometer to stabilize before reading.
20
Energize
Screen
Terminals
Message
a
O/B
Cool On
a
Y, G, O/B
b
Y, Y2
, G,
a
O/B
a
O/B
Heat On
a
Y, G, O/B
c
Auxiliary
Y, W1
, G,
Heat On
a
O/B
b
Y, Y2
,
d
W1
, G,
a
O/B