Installer Setup - Honeywell TB7220 COMMERCIALPRO Product Data

Programmable thermostat
Hide thumbs Also See for TB7220 COMMERCIALPRO:
Table of Contents

Advertisement

Installer
Setup

Installer Setup

Number
Name
a
Clock Format
0640
0650
Extended Fan
On time Heat
0660
Extended Fan
On time Cool
0670
Keypad Lockout
0680
Temperature Control
Heat
0685
Recovery Heat
Ramp Rate
0690
Temperature Control
Cool
0695
Recovery Cool
Ramp Rate
0700
Temperature Display
Offset
0710
Restore Factory
Defaults
INSTALLER SYSTEM TEST ITEMS
Test 1
Installer Test
Cool
Test 2
Installer Test
Fan
Test 3
Installer Test
Heat
Test 4
Installer Test
Auxiliary Heat
Test 8
Installer Test
TOD/Economizer
a
Setting available for modification in both the Installer and User setup modes.
NOTE: Press the Done button to exit the Installer System Test.
Table 6. Installer Setup Menu. (Continued)
Default
Setting
All Settings
12
12—12 Hour
24—24 Hour
0
0—Off
90—90 seconds
0
0—Off
40—40 seconds
0
0—Unlocked
1—Partial Lockout 1
2—Partial Lockout 2
3—Fully Locked
2
1—Less Aggressive
2—Standard
3—More Aggressive
5
0-20°F/hour
2
1—Less Aggressive
2—Standard
3—More Aggressive
3
0-20°F/hour
0
-3 (-1.5)— -3°F (-1.5°C)
-2 (-1.0)— -2°F (-1.0°C)
-1 (-0.5)— -1°F (-0.5°C)
0 (0.0)—0°F (0.0°C)
1 (0.5)—1°F (0.5°C)
2 (1.0)— 2°F (1.0°C)
3 (1.5)—3°F (1.5°C)
0
0—No
1—Yes
0
0—Off
1—Cool Stage 1
2—Cool Stage 2
0
0—Off
1—Fan On
0
0—Off
1—Heat Stage 1
2—Heat Stage 1 and 2
3—Heat Stage 1,2 and 3
0
0—Auxiliary Heat Off
1—Auxiliary Heat On
0
0—TOD/Economizer Off
1—TOD/Economizer On
15
TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
Not displayed with fan set to fossil or with cool-only
systems
Only shown if system has cool stages.
Unlocked: All functions accessible.
Partial 1: Locks all but Holiday, Override, and Up/Down.
Partial 2: Locks all but Holiday and Override.
Full: Entire interface locked/non-functional.
Only shown if system has heat stages.
Only integral gains affected. Affects control operation in all
control regimes (not just recovery or setpoint change).
More Aggressive stops signal prior to reaching the setpoint.
(For use with oversized equipment.)
Only shown if system has heat stages.
0 disables ramped recovery (step setpoint change at period
start time)
Only shown if system has cool stages.
Only integral gains affected. Affects control operation in all
control regimes (not just recovery or setpoint change).
More Aggressive stops signal prior to reaching the setpoint.
(For use with oversized equipment.)
Only shown if system has cool stages.
0 disables ramped recovery (step setpoint change at period
start time)
This offset applies to both the control temperature and to
the display temperature for indoor sensor (and remote
indoor sensor)
Resets all Installer Setup parameters to default values and
resets the schedule to the default energy-saving program.
Retains only calendar settings and time.
Notes
63-2635—03