Minimum Circuit
Capacity
Table 11 describes the typical
MCA levels of a standard unit
ventilator with the necessary
voltage and amp add-ons for
unit mounted controls.
42
Electrical Data
Table 11: MCA levels for standard and hi-static motor unit ventilators
Standard UV
Unit Size
HP
075
1/6 (.17)
100
1/6 (.17)
125
1/4 (.25)
150
1/4 (.25)
200
1/3 (.75)
Hi-Static Motor UV
Unit Size
Amps
075
2.5
100
2.5
125
2.7
150
2.7
200
5.7
For Trane
Controls, add
the following
values to
determine
TOTAL MCA
HP
Amps
1/3 (.33)
4.8
1/3 (.33)
4.8
1/2 (.50)
7.0
1/2 (.50)
7.0
3/4 (.75)
8.1
UV with Controls
Volts
Amps
120
0.94
208
0.55
240
0.48
277
0.41
480
0.41
UV-SVN002-EN