Download Print this page

Checkout - Honeywell R7824 Product Data

Amplifiers for 7800 series and r7140 relay modules

Advertisement

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 AMPLIFIERS FOR 7800 SERIES AND R7140 RELAY MODULES
7. Disconnect power supply before making wiring connec-
tions to prevent electrical shock and equipment damage.
8. All wiring must comply with appropriate electrical codes,
ordinances and regulations including NEC Class 1 (Line
Voltage) wiring where required.
9. Use recommended wire size and type no. 18 copper
conductors TTW(60C) or THW (75C) or THNN(90C).
10. Use recommended wire routing:
a. Keep the flame signal leadwire as short as possible
from the detector to the 7800 SERIES and R7140
Relay Module. The maximum permissible leadwire
length depends on the type of leadwire, conduit type
and leadwire diameter. The ultimate limiting factor for
flame signal leadwire length is the flame signal volt-
age.
b. Do not run high voltage ignition transformer wires in
the same conduit with the flame detection wiring.
c. If the flame detector leadwires are not long enough
to reach the 7800 SERIES and R7140 Relay Module
electrical connectors, make splices in a junction box.
(1) Enclose scanner wiring without armor cable in
metal cable or conduit.
(2) Follow flame detector Instructions.
11. Check wiring, see Fig. 3.
12. Install 7800 SERIES and R7140 Relay Module.
13. Restore power to the 7800 SERIES and R7140 Relay
Module.
Flame detector wiring is shown in Fig. 3.

CHECKOUT

Preliminary Inspection
Make certain that:
1. Wiring connections are correct and all terminal screws
and electrical connections are tight.
2. Proper flame failure response time is selected.
3. Amplifier is securely mounted on the 7800 SERIES and
R7140 Relay Module.
4. Detectors are properly positioned and cleaned according
to Detector Instructions.
5. Correct combination of amplifier and flame detector is
used.
Flame Signal Measurement (Fig. 4)
Flame signal can be measured at the Flame Signal Test Jacks,
see Fig. 4, and at the Keyboard Display Module. Measure the
flame signal at the appropriate times defined in the Checkout
section; see applicable 7800 SERIES and R7140 Relay
Module Instructions. See Table 3 for acceptable and maximum
flame signal voltage strengths.
CAUTION
Equipment Damage Hazard.
Improper wiring can destroy ultraviolet sensing
tube.
Carefully follow polarity sensitive wiring instructions for
the C7027, C7035, C7044, C7012, C7024, C7061,
C7961 and C7076. Reversing the leadwires, even
momentarily, can destroy the ultraviolet sensing tube.
NEGATIVE (-)
METER LEAD
FLAME SIMULATOR
TEST JACK
Fig. 4. Flame signal measurement with meter.
1. Connect blue leadwire from detector to terminal F and
white leadwire from C7027/C7035/C7044/C7061 to ter-
minal G.
2. Connect blue leadwire from detector to terminal F and
yellow leadwire from C7012/C7024/C7961 to terminal G.
3. Follow lightoff Instructions for applicable 7800 SERIES
and R7140 Relay Module.
Measuring Flame Signal With
Keyboard Display Module
Consult Instructions for applicable 7800 SERIES and R7140
Relay Module or Keyboard Display Module.
Measuring Flame Signal with a Volt
Ohmmeter
Two test jacks, positive and negative (Com) are accessible on
the top of the amplifier when plugged into the 7800 SERIES
and R7140 Relay Module. These jacks are provided for
monitoring flame signal strength. Use a one megohm/volt
meter to measure the flame signal strength. Connect the
positive meter lead (red) to the positive (+) amplifier test jack
and the negative meter lead (black) to the negative (-) amplifier
test jack. The test jacks use standard 0.180 inch diameter
voltmeter probes. A minimum 1.25 Vdc flame signal is
required.
NOTE: The probes need to tip toward the relay module in
order to make electrical contact.
7
POSITIVE (+)
METER LEAD
ONE
MEGOHM/VOLT
METER
M11459A
65-0109—14

Hide quick links:

Advertisement

loading

This manual is also suitable for:

R7847R7848R7849R7851R7852R7861 ... Show all