Typical Wiring Hookups - Honeywell Q7300A Installation Instructions Manual

Series 2000 commercial thermostat subbases
Hide thumbs Also See for Q7300A:
Table of Contents

Advertisement

Q7300A,C,D,G SERIES 2000 COMMERCIAL THERMOSTAT SUBBASES

Typical Wiring Hookups

RC
L1
(HOT)
L2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A SYSTEM WITH ONE TRANSFORMER.
3
CONNECT GND TO EARTH GROUND.
4
INSTALL FIELD JUMPER BETWEEN X4 AND X TO POWER LEDS.
62-0135
Y1
G
X
W1
RH
2
COMPRESSOR
CONTACTOR
HEAT
RELAY
FAN
RELAY
1
COOLING
TRANSFORMER
Fig. 9. Typical hookup of T7300D,F/Q7300A in one-stage heat and
one-stage cool conventional system with two transformers.
RC
Y1
2
COMPRESSOR
CONTACTOR 1
L1
(HOT)
L2
1
COOLING
TRANSFORMER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED
ON A SYSTEM WITH ONE TRANSFORMER.
Fig. 10. Typical hookup of T7300D,F/Q7300A in two-stage heat and
one-stage cool conventional system with two transformers.
SUBBASE
X4
X3
X1
C5
C4
4
EQUIPMENT
MONITOR 2
CA5
CA4
T7147 REMOTE COMFORT ADJUST MODULE
EQUIPMENT
MONITOR 1
HEATING
TRANSFORMER
SUBBASE
G
X
W2
W1
HEAT
RELAY 2
FAN
HEAT
RELAY
RELAY 1
4
C3
C2
C1
T
T
CA2
CA1
CA3
T
T
GND
3
1
L1
(HOT)
L2
M4939A
RH
1
L1
(HOT)
L2
HEATING
TRANSFORMER
M10230