Honeywell TH7000 Series Installation Manual page 8

Touch-screen programmable thermostat
Hide thumbs Also See for TH7000 Series:
Table of Contents

Advertisement

Installation Guide
Installer setup
Setup functions
Shaded areas below apply only to TH7220.
0240
First stage heat
cycle rate (CPH=
cycles per hour)
0250
Second stage heat
cycle rate (CPH)
0270
Emergency heat
cycle rate (CPH)
0280
Backlight
0300
Manual/Auto
changeover
0310
Auto changeover
deadband
0320
Temperature
display
0330
Daylight savings
0340
Remote sensor
0350
Heat pump
compressor lockout
0360
Heat pump
auxiliary lockout
69-2668—03
Settings & Options
5
Gas or oil furnaces of less than 90% efficiency
1
Steam or gravity systems
3 Hot water systems & furnaces of 90%+ efficiency
9 Electric furnaces
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
5
Gas or oil furnaces of less than 90% efficiency
1
Steam or gravity systems
3
Hot water systems & furnaces of 90%+ efficiency
9
Electric furnaces
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
9
Electric emergency heat
1
Steam or gravity systems
3
Hot water systems & furnaces of 90%+ efficiency
5
Gas or oil furnaces of less than 90% efficiency
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
0
Backlight on for approx. 8 seconds after keypress
1
Backlight always on low intensity, full bright after keypress
(requires 24VAC connection)
0
Manual changeover (Heat/Cool/Off)
1
Automatic changeover (Heat/Cool/Auto/Off)
3
Heat/cool temperature 3 °F apart (1.5 °C)
[Other options: 2-9 (2 °F to 9 °F/1 °C to 5 °C)]
0
Fahrenheit
1
Celsius
2
Auto-change to daylight savings time (2007 and beyond,
for areas that use the new 2007 DST calendar)
1 Auto-change to daylight savings time (through 2006, and for
areas that do not use the new 2007 DST calendar)
0
Daylight savings time is turned off
0
No remote sensor
1
Outdoor sensor (display only)
2
Outdoor control sensor (select heat pumps)
3
Indoor sensor
0
No heat pump compressor lockout
Other options:
5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55, 60 °F
(-15 °C to 15.5 °C)
0
No heat pump auxiliary lockout
Other options:
5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55, 60, 65 °F
(-15 °C to 18.5 °C)
8
(factory default in bold)
Continued on next page
** See page 11
** See page 11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Th7220u