273 Branchport Avenue
Long Branch, N.J. 07740
(800) 631-2148
www.wheeelockinc.com
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
MODEL NUMBER: SPL
GENERAL:
The Four Zone Splitter is designed to be used with Wheelock's multi circuit SAFEPATH panels and it provides a means for
expanding a supervised audio output zone from one to four sub zones. The Four Zone Splitters are UL Listed under Standard 864,
Control Units for Fire Protective Signaling Systems. They are listed for indoor use only. Only 1 Four Zone Splitter can be connected
to each SAFEPATH channel. They are to be mounted inside the SAFEPATH panel enclosure onto the power supply printed circuit
board (PCB) cover. The splitter works with all of the Wheelock amplifier modules. If the splitter is used with a power amplifier, the
maximum power per sub zone cannot exceed what is listed in Table 1.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
SPECIFICATIONS: (Per UL 864)
Audio Output Voltage
Maximum Output Power Per Sub Zone
Power Input Voltage:
Audio Input/Output Voltage:
Input Current:
Audio Power In:
Audio Power Out:
MOUNTING INSTRUCTIONS:
Four Circuit SAFEPATH
1.
Attach the 4 PCB standoffs to the 4 mounting holes in the SAFEPATH Power Supply PCB cover (see Figure 1) by pushing
standoff into the hole until it locks into place as shown in Figure 2.
2.
Attach the Four Zone Splitter PCB on to the PCB standoffs so that the standoffs mate with the mounting holes on the PCB as
shown in Figure 2. Push the PCB until the board locks into the 4 standoffs
3.
Remove the old hole cover on the SAFEPATH Panel's Dead Front Panel that corresponds to the location of the new splitter
module by removing the 4 hole plugs on the cover. Save the 4 plugs to attach the new cover. (See Figure 3)
4.
Attach the Four Zone Splitter cover to the Dead Front Panel using the 4 hole plugs.
Copyright 2003, 2004 Wheelock, Inc. All rights reserved.
Thank you for using our products.
INSTALLATION INSTRUCTIONS
FOUR ZONE SPLITTER
(FOR MULTI CIRCUIT SAFEPATH PANELS)
Four Zone Splitter
Table 1:
25.0V
25.0W
24VDC
25.0VRMS, 70.7VRMS, 100.0VRMS, or 0.5VRMS
40mA Standby with no zones selected
190mA with all zones selected
100.0 Watts Maximum
100.0 Watts Maximum (See Table 1 for maximum watts per zone)
. All warnings are printed in bold capital letters.
SAA-40S/80S/80SE
70.7V
100.0V
70.0W
100.0W
SALL-15S
0.5V
30 Speaker Inputs
P83541 G
Sheet 1 of 6