Wheelock RMS-3R Installation Instructions

Remote microphone (dual circuit)

Advertisement

Quick Links

273 Branchport Avenue
Long Branch, NJ 07740
(732) 222-6880
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
MODEL NUMBERS:
RMS-3B
RMS-3R

GENERAL:

The Remote Microphones are UL Listed under Standard 864, Control Units for Fire-Protective Signaling Systems. They are Listed
for indoor use only. The Remote Microphone is designed to be used with Wheelock's Dual Zone SAFEPATH Panel model DCSP.
It provides a means for making emergency voice announcements from an auxiliary location.
connected to the SAFEPATH Panel. The hand held push to talk microphone is supervised to ensure proper connection. It is not
replaceable. If it is detached from the unit, the unit must be returned for repair.
READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT.

SPECIFICATIONS:

Power Input Voltage:
Audio Output Level:
Output Impedance:
Input Current:

WIRING DIAGRAM:

WIRING SPECIFICATIONS:

Cable Size:
Maximum Length:
Maximum Capacitance:
Copyright 1997, 1998 Wheelock, Inc. All rights reserved.
Thank you for using our products.
INSTALLATION INSTRUCTIONS
REMOTE MICROPHONE (DUAL CIRCUIT)
Remote Microphone Dual Circuit Black
Remote Microphone Dual Circuit Red
20-31VDC
1.05V RMS
600 Ohms
50mA
14 - 22 AWG Shielded. The shield must be connected only at the SAFEPATH Panel.
1000 Feet
.05uF/Total Run (50pF/foot for 1000 FT.)
Figure 1.
Only 1 Remote Microphone can be
Sheet 1 of 5
P83542 B

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RMS-3R and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Wheelock RMS-3R

  • Page 1 The Remote Microphones are UL Listed under Standard 864, Control Units for Fire-Protective Signaling Systems. They are Listed for indoor use only. The Remote Microphone is designed to be used with Wheelock’s Dual Zone SAFEPATH Panel model DCSP. It provides a means for making emergency voice announcements from an auxiliary location.
  • Page 2 MOUNTING INSTRUCTIONS: Figure 2. 1. Install a 4” gang backbox (either flush or surface) to the desired location. Be sure that the mounting box is level. 2. Attach the 6 wires as shown in the wiring diagram (Figure 1). Be sure to use the specified wire. 3.
  • Page 3 Figure 3. 1. The key must be inserted and turned to the ON position for the controls to function. The key is removable only in the OFF position. 2. The status LEDs reflect the system’s condition regardless of the key position. The green LED indicates there are no faults in the SAFEPATH system.
  • Page 4 DESCRIBING THE PRODUCT FOR USE IN PROMOTIONAL OR ADVERTISING CLAIMS, OR FOR ANY OTHER USE, INCLUDING DESCRIPTION OF THE PRODUCT'S APPLICATION, OPERATION, INSTALLATION AND TESTING IS USED AT THE SOLE RISK OF THE USER AND WHEELOCK WILL NOT HAVE ANY LIABILITY FOR SUCH USE. P83542 B...
  • Page 5: Limited Warranty

    ON ANY CLAIM OF ANY KIND SHALL CEASE IMMEDIATELY UPON THE INSTALLATION IN THE PRODUCT OF ANY PART NOT FURNISHED BY WHEELOCK. IN NO EVENT SHALL WHEELOCK BE LIABLE FOR ANY CLAIM OF ANY KIND UNLESS IT IS PROVEN THAT OUR PRODUCT WAS A DIRECT CAUSE OF SUCH CLAIM. FURTHER, IN NO EVENT, INCLUDING IN THE CASE OF A CLAIM OF NEGLIGENCE, SHALL WHEELOCK BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES.

This manual is also suitable for:

Rms-3b

Table of Contents