Installation Guide
Wiring
Wiring guide — conventional systems
Shaded areas below apply only to
1H/1C System
(1 transformer)
Rc
Power
[1]
R
[R+Rc joined by jumper]
Y
Compressor contactor
C
24VAC common [3]
W
Heat relay
G
Fan relay
Heat-only System
Rc
Power
[1]
R
[R+Rc joined by jumper]
C
24VAC common [3]
W
Heat relay
Heat-only System
(Series 20)
[5]
Rc
[R+Rc joined by jumper]
R
Series 20 valve terminal "R" [1]
Y
Series 20 valve terminal "W"
24VAC common [3]
C
W
Series 20 valve terminal "B"
Heat-only System
(normally open zone valve)
Rc
[R+Rc joined by jumper]
R
Power
[1]
Y
Normally open zone valve
C
24VAC common [3]
1H/1C System
(2 transformers)
Rc
Power (cooling transformer)
R
Power (heating transformer)
Y
Compressor contactor
C
24VAC common [3, 4]
W
Heat relay
G
Fan relay
NOTES
Wire specifications:
Use 18- to 22-gauge thermostat wire.
Shielded cable is not required.
[1]
Power supply. Provide disconnect means
and overload protection as required.
[2]
Remove jumper for 2-transformer systems.
[3] Optional 24VAC common connection.
[4]
Common connection must come from
cooling transformer.
[5] In Installer Setup, set system type to
Heat Only.
[6] In Installer Setup, set system type to
2Heat/2Cool Conventional.
69-1922EFS—01
TH5320U/TH5220D
G
W
C
Y
R
Rc
M29372
W
C
R
Rc
M29373
W
C
Y
R
Rc
M29374
C
Y R
Rc
[5]
M29375
G
W
C
Y
R
Rc
M29376
[1, 2]
[1, 2]
or as otherwise noted.
Heat-only System
with Fan
Rc
Power
[1]
R
[R+Rc joined by jumper]
C
24VAC common [3]
W
Heat relay
G
Fan relay
Cool-only System
Rc
Power
[1]
R
[R+Rc joined by jumper]
Y
Compressor contactor
C
24VAC common [3]
G
Fan relay
2H/2C System
(1 transformer)
[6]
Rc
Power
[1]
R
[R+Rc joined by jumper]
Y
Compressor contactor (stage 1)
C
24VAC common [3]
W
Heat relay (stage 1)
G
Fan relay
W2
Heat relay (stage 2)
Y2
Compressor contactor (stage 2)
2H/2C System
(2 transformers)
[6]
Rc
Power (cooling
R
Power (heating transformer)
Y
Compressor contactor (stage 1)
C
24VAC common [3, 4]
W
Heat relay (stage 1)
G
Fan relay
W2
Heat relay (stage 2)
Y2
Compressor contactor (stage 2)
See
[notes]
below
[7] In Installer Setup, set changeover valve to
O or B.
[8] In Installer Setup, set system type to
2Heat/1Cool Heat Pump.
[9] In Installer Setup, set system type to
2Heat/2Cool Heat Pump.
[10] In Installer Setup, set system type to
3Heat/2Cool Heat Pump.
[11]
L terminal sends a continuous output when
thermostat is set to Em. Heat. Connect
to Honeywell zoning panels to switch the
panel to Emergency Heat.
[12]
Install field jumper between Aux and E if
there is no emergency heat relay.
4
G
W
C
R
Rc
M29377
G
C
Y
R
Rc
M29378
Y2
W2
G
W
C
Y
R
Rc
M29379
Y2
W2
G
W
C
Y
R
Rc
M29380
transformer) [1, 2]
[1, 2]

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Focuspro th5110dFocuspro th5220dFocuspro th5320u

Table of Contents