Combustion Air And Ventilation Appliances; In Unconfined Spaces; In Confined Spaces - Kenmore POWER MISER 153.331712HA Owner's Manual

Table of Contents

Advertisement

Combustion
Air and Ventilation
for
Appliances
Located
in Unconfined
Spaces
UNCONFINED
SPACE is space whose volume is not less than
50 cubic feet per 1,000 Btu per hour (4.8 m 3 per kW) of the
aggregate input rating of all appliances installed in that space.
Rooms communicating
directly with the space in which the
appliances
are installed, through openings not furnished with
doors, are considered a part of the unconfined space.
In unconfined spaces in buildings, infiltration may be adequate
to provide air for combustion,
ventilation
and dilution of flue
gases.
However, in buildings of tight construction (for example,
weather stripping, heavily insulated, caulked, vapor barrier, etc.),
additional
air may need to be provided
using the methods
described
in Combustion
Air and Ventilation
for Appliances
Located in Confined Spaces.
Combustion
Air and Ventilation
for
Appliances
Located
in Confined
Spaces
CONFINED
SPACE is a space whose volume
is less than
50 cubic feet per 1,000 Btu per hour (4.8 m3 per kW)
of the
aggregate input rating of all appliances installed in that space.
A. ALL AIR FROM INSIDE BUILDINGS:
(See Figure 9 on page 10 and Figure 10 below)
The confined
space shall be provided
with two permanent
openings
communicating
directly with an additional
room(s)
of sufficient volume so that the combined volume of all spaces
meets the criteria for an unconfined space.
The total input of
all gas utilization equipment
installed in the combined space
shall
be considered
in making this determination.
Each
opening shall have a minimum free area of one square inch
per 1,000 Btu per hour (22 cm2/kW) of the total input rating of all
gas utilization equipment
in the confined space, but not less
than
100 square
inches
(645 cm2).
One opening
shall
commence
within
12 inches
(30 cm) of the top and one
commencing
within 12 inches (30 cm) of the bottom of the
enclosures.
CHIMNEY OR
VENTILATION
LOUVERS
(EACH END OF ATTIC)
OUTLET AIR
WATER HEATER
FURNACE
INLET AIR DUCT
ALT.
INLET
AIR
VENTILATION
LOUVERS
RGURE11.
When directlycommunicating with the outdoors, each opening
shall have a minimum free area of 1 square inch per 4,000 Btu
per hour (5.5 cm2/kW) of total input rating of all equipment in the
enclosure. See Figure 12.
When communicating
with the outdoors
through vertical
ducts, each opening
shall have a minimum
free area of
1 square inch per 4,000 BTU per hour (5.5 cm2/kW) of total
input
rating
of all equipment
in the enclosure.
See
Figure 12.
VENTILATION
LOUVERS
(EACH
END OF ATTIC)
" FURNACE
INLET AIR DUCT
(ENDS 1' OR 30 crn
ABOVE FLOOR)
NT
FURNACE
WATER
INGS
ER
r
i
i
i
i
i
i
z
J
I
I
,
,
_
i
=
i
FIGURE10.
B. ALL AIR FROM OUTDOORS:
(See Figures 9, 11,12 and 13)
The confined
space shall be provided
with two permanent
openings, one commencing
within
12 inches (30 cm) of the
top and one commencing
within 12 inches (30 cm) from the
bottom of the enclosure.
The openings
shall communicate
directly, or by ducts, with the outdoors or spaces (crawl or attic)
that freely communicate
with the outdoors.
RGURE12,
When communicating
with the outdoors through horizontal
ducts, each opening shall have a minimum free area of 1
square inch per 2,000 BTU per hour (11 cm2/kW) of total
input
rating
of all equipment
in the enclosure.
See
Figure 13.
11
II II
WATER
HEATER
III T !!!
i
:': :.,:
P I
(
RGURE13.
OUTLET AIR DUCT
INLET AIR DUCT

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Power miser 153.331740153.331740Power miser 12

Table of Contents